Event Message Help Text
133
TRANSFER INHIBITED
Transfer Inhibited
Uninterrupted transfer between sources is inhibited due to input source failure, sources out of sync, switch failure, or the
unit is in bypass mode.
Check the Event Log for the event or events that may have caused the alarm.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2
system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and
press RETURN on your keyboard.
OUTPUT UV
Output Undervoltage
The voltage being supplied to the load has dropped below the acceptable nominal voltage. Check the input voltage from
both sources.
This event and the system status surrounding it have been written to a History Log if the History Logs were not already full.
This event was also written to the Event Log, if so configured.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2
system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and
press RETURN on your keyboard.
INPUT CONTACT #1
Input Contact Isolator #1
Occurrence of the indicated external event has been detected by Input Contact Isolator #1 of the Open Comms Digital Input
option board.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the Liebert STS2
system from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.
The event, with its assigned name, was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type CA and
press RETURN on your keyboard.