Appendix D.2. Metasys DC9100 Memory Map
Note: The DC9100 is not currently supported by the FieldServer MetasysN2 Driver.
The information below is for interest and future use only.
PAGE 0
Item
DEC
Item
HEX
Signal Condition
Read/
Write
Johnson
Tag
Description
0
0
Byte Read MODL
Device model. Value always either 2 or
12
1
1
FP Read INP1 Analog input 1
2
2
FP Read INP2 Analog input 2
3
3
FP Read INP3 Analog input 3
4
4
FP Read INP4 Analog input 4
5
5
FP Read INP5 Analog input 5
6
6
FP Read INP6 Analog input 6
7
7
FP Read INP7 Analog input 7
8
8
FP Read INP8 Analog input 8
9
9
FP Read NCM1 Numeric calculation modul result
10
A FP Read NCM2 Numeric calculation modul result
11
B FP Read NCM3 Numeric calculation modul result
12
C FP Read NMC4 Numeric calculation modul result
13
D FP Write REC1 Remote constant 1
14
E FP Write REC2 Remote constant 2
15
F FP Write REC3 Remote constant 3
16
10
FP Write REC4 Remote constant 4
17
11
FP Write OUT1 Control output 1
18
12
FP Write OUT2 Control output 2
19
13
FP Write OUT3 Control output 3
20
14
FP Write OUT4 Control output 4
21
15
FP Write OUT5 Control output 5
22
16
FP Write OUT6 Control output 6
23
17
FP Write OUT7 Control output 7
24
18
FP Write OUT8 Control output 8
25
19
FP Write WSP1 Working setpoint 1
26
1A FP Write WSP2 Working setpoint 2
27
1B FP Write WSP3 Working setpoint 3
28
1C FP Write WSP4 Working setpoint 4
29
1D FP Write WSP5 Working setpoint 5
30
1E FP Write WSP6 Working setpoint 6
31
1F FP Write WSP7 Working setpoint 7
32
20
FP Write WSP8 Working setpoint 8
33
21
Word Read STW1 Status word 1
34
22
Word Read STW2 Status word 2
35
23
Word Read STW3 Status word 3
36
24
Word Read STW4 Status word 4
37
25
Word Read STW5 Status word 5
38
26
Word Read STW6 Status word 6
39
27
Word Read STW7 Status word 7
40
28
Word Read STW8 Status word 8
41
29
Word Write DOUT Logic output DDC control
42
2A Byte Write CHLD Hold mode control
43