FieldServer FS-8700-19 Computer Drive User Manual


 
FS-8700-19_Metasys_N2 Driver Manual Page 41 of 51
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
General dynamic Parameters
Relative Item Signal Condition Read/Write
Johnson Tag Description
B(4) DO6 TRIAC 6 ON
B(5) DO7 TRIAC 7 ON
B(6) DO1 TRIAC 1 ON
B(7) DO2 TRIAC 2 ON
B(8) Not used
32 Byte Read ROS TC9100 Operation Status
B(1) MODS 00 = Night mode
01 = Stand-by mode
10 = Comfort mode
B(2) 11 = OFF mode
B(3) MODT Temporary mode
B(4) MODA Alternate mode
B(5) Supervisory mode enabled
B(6) WIN Window open
B(7) OCC Occupancy Sense
B(8) AIRQ Air Quality Sense
33 Byte Write MSK Outputs Central Control - Enable
B(1) DO3E Enable TRIAC 3
B(2) DO4E Enable TRIAC 4
B(3) DO5E Enable TRIAC 5
B(4) DO6E Enable TRIAC 6
B(5) DO7E Enable TRIAC 7
B(6) DO1E Enable TRIAC 1
B(7) DO2E Enable TRIAC 2
34 Byte Write ODC Outputs Central Control - Set Level
B(1) DO3C TRIAC 3 ON
B(2) DO4C TRIAC 4 ON
B(3) DO5C TRIAC 5 ON
B(4) DO6C TRIAC 6 ON
B(5) DO7C TRIAC 7 ON
B(6) DO1C TRIAC 1 ON
B(7) DO2C TRIAC 2 ON
35 Byte Write HLD Control Loops Hold
B(1) Loop #1 Hold
B(2) Loop #2 Hold
B(3) Loop #3 Hold
B(4) Loop #4 Hold
B(5) Loop #5 Hold
B(6) Loop #6 Hold
36 Byte Write HLD Computer mode Control
B(1) Loop #1 Hold WSP override
B(2) Loop #2 Hold WSP override
B(3) Loop #3 Hold WSP override
B(4) Loop #4 Hold WSP override
B(5) Loop #5 Hold WSP override
B(6) Loop #6 Hold WSP override
37 Byte Write SUP Supervisory Mode Control
B(1) MODC 00 = Night mode request
01 = Stand-by mode request
10 = Comfort mode request
B(2) 11 = OFF mode request
B(3) SOFF Shut-Off mode request
B(4) STUP Start-Up mode request
B(5) Not used
B(6) Supervisory Mode Control
B(7) MAN Manual OP Mode