Item
DEC
Item
HEX
Signal Condition
Read/
Write
Johnson
Tag
Description
180
B4 Byte Write TYPE8 Controller type
181
B5 FP Write LS8 Local setpoint
182
B6 FP Write PB8 Proportional band
183
B7 FP Write TI8 Reset action
184
B8 FP Write TD8 Rate action
185
B9 FP Write HL8 Upper limit of the control output
186
BA FP Write LL8 Lower limit of the control output
187
BB FP Write BS8 Change of setpoint during STAND-BY
188
BC FP Write BO8 Change of setpoint during OFF
189
BD FP Write AD8 Deviation alarm
190
BE Byte Write IR1 Range analog input 1
191
BF FP Write HA1 High alarm input 1
192
C0 FP Write LA1 Low alarm input 1
193
C1 FP Write FI1 Filter time input 1
194
C2 Byte Write IR2 Range analog input 2
195
C3 FP Write HA2 High alarm input 2
196
C4 FP Write LA2 Low alarm input 2
197
C5 FP Write FI2 Filter time input 2
198
C6 Byte Write IR3 Range analog input 3
199
C7 FP Write HA3 High alarm input 3
200
C8 FP Write LA3 Low alarm input 3
201
C9 FP Write FI3 Filter time input 3
202
CA Byte Write IR4 Range analog input 4
203
CB FP Write HA4 High alarm input 4
204
CC FP Write LA4 Low alarm input 4
205
CD FP Write FI4 Filter time input 4
206
CE Byte Write IR5 Range analog input 5
207
CF FP Write HA5 High alarm input 5
208
D0 FP Write LA5 Low alarm input 5
209
D1 FP Write FI5 Filter time input 5
210
D2 Byte Write IR6 Range analog input 6
211
D3 FP Write HA6 High alarm input 6
212
D4 FP Write LA6 Low alarm input 6
213
D5 FP Write FI6 Filter time input 6
214
D6 Byte Write IR7 Range analog input 7
215
D7 FP Write HA7 High alarm input 7
216
D8 FP Write LA7 Low alarm input 7
217
D9 FP Write FI7 Filter time input 7
218
DA Byte Write IR8 Range analog input 8
219
DB FP Write HA8 High alarm input 8
220
DC FP Write LA8 Low alarm input 8
221
DD FP Write FI8 Filter time input 8
222
DE FP Write OH1 Output 1 high range
223
DF FP Write OL1 Output1 low range
224
E0 Byte Write OMS1 Source of analog output module 1
225
E1 FP Write OH2 Output 2 high range
226
E2 FP Write OL2 Output 2 low range
227
E3 Byte Write OMS2 Source of analog output module 2
228
E4 FP Write OH3 Output OUTA1 high range
229
E5 FP Write OL3 Output OUTA1 low range
230
E6 Byte Write OMS3 Source of logic output module OUTA