FieldServer FS-8700-19 Computer Drive User Manual


 
FS-8700-19_Metasys_N2 Driver Manual Page 7 of 51
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
4.2. Client Side Connection Descriptions
Section Title
Connections
Column Title Function Legal Values
Port
Specify which port the device is
connected to the FieldServer
P1-P8, R1-R2
1
Protocol Specify protocol used Metasys_N2
Baud* Specify baud rate
9600
Parity* Specify parity
None
Data_Bits* Specify data bits
8
Stop_Bits* Specify stop bits
1
Handshaking* Specify hardware handshaking
None
Poll _Delay* Time between internal polls
0
Line_Drive_On*
Duration of RTS assert before
start of transmission
0.001s
Line_Drive_Off*
Duration of RTS assert after
end of transmission
0.000s
Example
// Client Side Connections
Connections
Port, Protocol
R1, Metasys_N2
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction