FieldServer FS-8700-19 Computer Drive User Manual


 
FS-8700-19_Metasys_N2 Driver Manual Page 36 of 51
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
PAGE 0
Item
DEC
Item
HEX
Signal Condition
Read/
Write
Johnson
Tag
Description
135
87
FP Write AD5 Deviation alarm
136
88
Byte Write PV6@ Process variable connection
137
89
Byte Write RS6@ Remote setpoint connection
138
8A Byte Write RV6@ Reference variable connection
139
8B Byte Write PB6@ Proportional band connection
140
8C Byte Write OF6@ OFF mode logic control connection
141
8D Byte Write SB6@
STAND-BY mode logic control
connection
142
8E Byte Write RA6@ Reverse action logic control connection
143
8F Byte Write EF6@
External forcing logic control
connection
144
90
Byte Write TYPE6 Controller type
145
91
FP Write LS6 Local setpoint
146
92
FP Write PB6 Proportional band
147
93
FP Write TI6 Reset action
148
94
FP Write TD6 Rate action
149
95
FP Write HL6 Upper limit of the control output
150
96
FP Write LL6 Lower limit of the control output
151
97
FP Write BS6 Change of setpoint during STAND-BY
152
98
FP Write BO6 Change of setpoint during OFF
153
99
FP Write AD6 Deviation alarm
154
9A Byte Write PV7@ Process variable connection
155
9B Byte Write RS7@ Remote setpoint connection
156
9C Byte Write RV7@ Reference variable connection
157
9D Byte Write PB7@ Proportional band connection
158
9E Byte Write OF7@ OFF mode logic control connection
159
9F Byte Write SB7@
STAND-BY mode logic control
connection
160
A0 Byte Write RA7@ Reverse action logic control connection
161
A1 Byte Write EF7@
External forcing logic control
connection
162
A2 Byte Write TYPE7 Controller type
163
A3 FP Write LS7 Local setpoint
164
A4 FP Write PB7 Proportional band
165
A5 FP Write TI7 Reset action
166
A6 FP Write TD7 Rate action
167
A7 FP Write HL7 Upper limit of the control output
168
A8 FP Write LL7 Lower limit of the control output
169
A9 FP Write BS7 Change of setpoint during STAND-BY
170
AA FP Write BO7 Change of setpoint during OFF
171
AB FP Write AD7 Deviation alarm
172
AC Byte Write PV8@ Process variable connection
173
AD Byte Write RS8@ Remote setpoint connection
174
AE Byte Write RV8@ Reference variable connection
175
AF Byte Write PB8@ Proportional band connection
176
B0 Byte Write OF8@ OFF mode logic control connection
177
B1 Byte Write SB8@
STAND-BY mode logic control
connection
178
B2 Byte Write RA8@ Reverse action logic control connection
179
B3 Byte Write EF8@
External forcing logic control
connection