Input Output Config Parameters
Relative Item Signal Condition
Read/Write
Johnson Tag
Description
162 FP Write WA Winter Authority Slope
163 FP Write SA Summer Authority Slope
164 Byte R/W FT@ Freeze Temperature connection
165 FP Write FSP Freeze set point
166 FP R/W FDIF Freeze Differential
167 Word Write LOO Input/Output Override Control
W(1) Read Three Speed Fan Actual Speed
00 = Output OFF
01 = Speed #1
10 = Speed #2
W(2) Read 11 = Speed #3
W(3) Not used
W(4) Read FOS Three spd Fan Overrd Reqst by Hardware
W(5) Write Fan Speed Reqst by Command Module
00 = Output OFF
01 = Speed #1
10 = Speed #2
W(6) 11 = Speed #3
W(7) TM9100 Real Time Clk Refresh Request
W(8) FOR Three speed Fan Overrd Reqst Cmd Mod
W(9) AIO1 Analog Input #1 Override
W(10) AIO2 Analog Input #2 Override
W(11) AIO3 Analog Input #3 Override
W(12) AIO4 Analog Input #4 Override
168 Word Write CLACT Control Loops Activity Mode
W(1) Read Loop #1 Heating
W(2) Read Loop #2 Heating
W(3) Read Loop #3 Heating
W(4) Read Loop #4 Heating
W(5) Read Loop #5 Heating
W(6) Read Loop #6 Heating
W(7) Not used
W(8) Not used
W(9) Write Loop #1 Active
W(10) Write Loop #2 Active
W(11) Write Loop #3 Active
W(12) Write Loop #4 Active
W(13) Write Loop #5 Active
W(14) Write Loop #6 Active
169 Word R/W ALG2 Configuration Index 2
170 FP R/W WAL Winter Authority Limit
171 FP R/W SAL Summer Authority Limit
Items Stored in the TM91xx External Database
Relative Item Signal Condition Read/Write
Johnson Tag Description
256 Byte Read UNIT Device Model : xxH
257 FP Read TEMP Room Temperature
258 FP Read RSP Remote Temperature Set Point
259 Word Read LOO Copy of TC9100 Item LOO
260 Byte Read JMP TM9100 Jumper Configuration & status
B(1) JMP1 Clock Setting Disable
B(2) JMP2 Fan Setting Disable
B(3) JMP3 Time Schedule Setting Disable
B(4) JMP4 Model with Time Schedule
B(5) JMP5 Time Schedule Configuration Changed
261 Word Write TIME Real Time
W(1) RTC Minutes 0..59