Appendix E. Error Messages
Error Message Description and Action
MN2:#01 WARN.
Server_Hold_Timeout is
%0.3fs
For N2Open Slave
typical value is %0.3fs
Typically N2open Clients are configured to timeout after 200ms. If a
FieldServer is configured as a Server the Server_Hold_Timeout time
should be set to 0.175s or less otherwise the response will be suppressed.
This message is printed if the Server_Hold_Timeout is set for >0.175s.
If the Client’s timeout is >200ms this message may be ignored.