Input Output Config Parameters
Relative Item Signal Condition
Read/Write
Johnson Tag
Description
W(14) Read Reset Cycle indication
W(15) Read 00 = Power Up Reset
01 = External Reset
10 = Oscillator Failure
W(16) Read 11 = Watchdog Reset
133 Word R/W TCS2 TC9100 Controller Options
W(1) 00 Select Analog Input 1 ADC
to
W(2) 11 Select Analog Input 4 ADC
W(3) TM9100 does not overrd the proc Variable
W(4) Half Alternate Mode Timing
W(5) 0 = Celsius 1 = Fahrenheit
W(6) 0 = 50 Hz 1 = 60 Hz Power Line
W(7) Enable Facilitator Mode
W(8) TRIAC7 is ON if mode is Comfort
W(9) Digital Input #1 Mode
000 = Not used
001 = Window Open
010 = Occupancy Sensor
011 = Air Quality Sensor
100 = Reverse Action
W(11) 101 = Intrusion Alarm
W(12) Negate Digital Input #1
W(13) Digital Input #2 Mode
000 = Not used
001 = Window Open
010 = Occupancy Sensor
011 = Air Quality Sensor
100 = Reverse Action
W(15) 101 = Intrusion Alarm
W(16) Negate Digital Input #2
134 Word R/W TCS3 Enable Jumper Options
W(1) Enable Integral Zeroing Loop #1
W(2) Enable Integral Zeroing Loop #2
W(3) Enable Integral Zeroing Loop #3
W(4) Enable Integral Zeroing Loop #4
W(5) Enable Integral Zeroing Loop #5
W(6) Enable Integral Zeroing Loop #6
W(7) Not used
W(8) Not used
W(9) Enable Gain Doubling Loop #1
W(10) Enable Gain Doubling Loop #2
W(11) Enable Gain Doubling Loop #3
W(12) Enable Gain Doubling Loop #4
W(13) Enable Gain Doubling Loop #5
W(14) Enable Gain Doubling Loop #6
135 Byte Write TCS1 Controller Options
B(1) Not used
B(2) Not used
B(3) Not used
B(4) Not used
B(5) Not used
B(6) Not used
B(7) Not used
B(8) Default Action 1=Reverse
136 Word R/W HDW1 Hardware Configuration
137 FP R/W HRI1 High Range AI1