FieldServer FS-8700-64 Computer Drive User Manual


 
FS-8700-64 ATMI ACM Page 18 of 22
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Malfunction Major Type Mafunction Minor Type
1. INADEQUATE BYPASS FLOW 0.
2. EMERGENCY SWITCH
CLOSURE
1.TEMP_LOW
2. TEMP_HIGH
3. LOSS_OF_NH3_FLOW
3. FAILED LEAK CHECK 0.
4. DSP FAILURE in module 0.
5. FAILURE to get interferogram
1. Bench timeout
2. Bench short scan
3. Zero ZPD value or address
4. Bench reports Bad Scan
5. Bench DREQ stuck TRUE
6. Energy (ZPD) address out of
range
7. energy (ZPD) value too high
8. energy (ZPD) value too low
9. DSP reports bad scan
6.8 Gas Values & Scaling
The driver stores all gas values after multiplying them by 100. This allows the driver to store
values in arrays with formats other than floats without losing the precision provided by the ACM
unit. This is done because some downstream devices’ and protocols cannot handle floating
point numbers. This may not suite you in which case you will need to use scaling.
These parameter keywords should be added to each CSV Map Descriptor definition.
…..Data_Array_Low_Scale, Data_Array_High_Scale, Device_Low_Scale,
Device_High_Scale…….
To store the actual values reported by the ACM unit you should use the following values :
…..Data_Array_Low_Scale, Data_Array_High_Scale, Device_Low_Scale,
Device_High_Scale…….
…..0 , 1 , 0 , 100…..
6.9 Alarms and/or Warnings
The following list are valid entries in specifying the ATMI_Data parameter in the csv file.
Slot-alarm,
Slot-warning,
Slot-combo
Port-alarm,
Port-warning,
Port-combo