FieldServer FS-8700-64 Computer Drive User Manual


 
FS-8700-64 ATMI ACM Page 6 of 22
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Example
The following FieldServer settings are suitable for default ACM settings.
// Client Side Connections
Connections
Port, Baud, Parity, Protocol, Handshaking, Poll_Delay
P8, 9600, None, ATMI , None, 0.100s
4.3 Client Side Nodes
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node Up to 32 alphanumeric
characters
Node_ID ACM units do not have a
node ID contained in the
serial data. This field s not
used in the ATMI ACM
driver.
Protocol Specify protocol used ATMI
Port Specify which port the
device is connected to the
FieldServer
P1-P8, R1-R2
Example
// Client Side Nodes
Nodes
Node_Name, Protocol, Port
ACM-1 , ATMI , P8
4.4 Client Side Map Descriptors
4.4.1 FieldServer Specific Map Descriptor Parameters
Column Title Function Legal Values
Map_Descriptor_Name Name of this Map Descriptor Up to 32 alphanumeric
characters
Data_Array_Name Name of Data Array where
data is to be stored in the
FieldServer
One of the Data Array
names from “Data Array”
section above
Data_Array_Location Starting location in Data
Array
0 to maximum specified in
“Data Array” section above
Function Function of Client Map
Descriptor
PASSIVE