GE 20 Power Supply User Manual


 
g
GE
OPM_SGS_USM_10K_40K_0US_V010.doc 35/88 Operating Manual
SG Series
10, 20, 30 & 40 kVA
6.6 EVENTS (ALARMS AND MESSAGES)
Each of the following listed events can be displayed on the LCD screen or on PC where the
ARGUS/JumpManager - Control Network is installed.
Alarms and Messages are differently specified because the alarms are indicating an
abnormal functioning of the UPS (which are additionally signaled with the LED alarm and
acoustically with the buzzer), while the messages indicate the various states of operation of
the UPS (stored in the events list, but no activating the LED alarm and the buzzer).
When in the alarms mode, the LCD screen displays a time ordered sequence of
screens corresponding to the last 256 alarms and messages, each screen indicating:
The number of the event (255 = the most recent).
The date and time when the event occurred.
The standard code and the status word.
An explicit text description of the events.
6.6.1 Alarms list
Code Alarms Meaning
4000
SETUP VALUES
LOST
Parameters are lost and have been replaced with default
values.
Call nearest Service Center for intervention.
4004
UPS
FAILURE
The master unit detected the slave unit missing on the
communication bus even though switch Q1 is still closed.
4100
RECTIFIER FUSES
FAILURE
The u-switch mounted on the Rectifier Input Fuses indicates
a blown fuse, and consequently shut down.
Clearance of this condition allows you to restart the Rectifier.
4102
K4 CLOSING
FAILURE
K4 not closed despite a closing command being issued.
Signaled by auxiliary contact.
Rectifier cannot start.
4103
K4 OPENING
FAILURE
K4 not open despite an opening command being issued.
Signaled by auxiliary contact.
Utility remains connected to Rectifier bridge.
4104
BATTERY
FUSES
This function, when enabled on input programmable relays
(password required), warns the user about the external
Battery Fuses failure or MCB opening, signalled by NO free
contact.
4105
RECTIFIER
OVERTEMPERATURE
Temperature sensor indicates an over temperature on the
Rectifier Bridge
.
Only alarm is given.
The Rectifier, when in Off state, cannot start as long as this
condition persists.
4106
RECTIFIER
TRANSFORMER
OVERTEMPERATURE
The temperature sensor inside the input transformer winding
indicates over temperature.
Only the alarm is given.
The Rectifier, when in Off state, cannot start as long as this
condition persists.
4110
RECTIFIER UTILITY
OUT OF TOLERANCE
Rectifier Input Utility is out of tolerance (voltage, frequency or
phase).