28 CIMPLICITY® Display Station Touch Display: IC752CTD400/450
March 1998 GFK-1425B
Display
Symptom Possible Causes Solution
Characters are dim. Computer screen is in direct light. Change lighting or adjust contrast.
Display is blank (PWR indicator is
lighted).
Screen has overheated. If Display Station is in direct
sunlight, move it and allow it to
cool.
Display Station is set up for
invalid video mode.
Reboot.
Windows NT models: select VGA
Mode
Windows 95 models: press
F8
when “Starting Windows 95”
appears, then select Safe Mode.
If Windows is now displayed, go
into Control Panel, Display
Settings, and change settings to
the correct video driver and mode.
Contact GE Fanuc’s
CIMPLICITY hotline for more
information.
Screen saver is active. Touch the touch screen, or a key
on the keypad.
Memory
Symptom Possible Causes Solution
Memory count during powerup
self-test is incorrect.
Optional SIMM is installed
incorrectly or is incompatible with
the Display Station CPU.
Make sure that the appropriate
memory is installed correctly.
Out of Memory
message is
displayed or insufficient memory
error occurs during operation.
System ran out of memory for the
application.
Check the memory requirements
for the application. (Refer to the
application documentation.)
Install additional memory.
Too many terminate and stay
resident (TSR) programs running.
Modify the startup folder to use
only those TSR applications that
are really needed.