GenTran ATS1001R Switch User Manual


 
11
SECTION 2 – COMPATIBLE EQUIPMENT
2.1 Compatible Generators
In order for the OVATION™ Series ATS to function as designed, it must
be connected to a permanently installed, automatic starting
generator, with a continuous supply of fuel, such as gasoline, diesel, LPG or natural gas. Additionally, gasoline or diesel-powered
generators must
be equipped with automatic choke and electric/remote start. All OVATION™ Series ATS systems supports 2-wire
(ON, +12V) or 4-wire (CRANK, ON, +12V, -12V) generator signaling.
Note: Many generators require additional control circuits to properly operate with OVATION™ Series ATS. Contact Gen/Tran or visit
http://www.gen-tran.com/content/support/installation_instructions.asp
, see: Ovation™ Series ATS – Generator Connection
Diagrams for additional information.
2.2 Compatible Circuit Breakers
Each OVATION™ Series ATS has been configured; factory tested and shipped with the UTILITY MAIN and GENERATOR MAIN circuit
breakers installed. Compatible branch circuit breakers (supplied by installer) are as follows:
COMPATIBLE CIRCUIT BREAKER TYPES:
Siemens QAF (arc fault), QFH, QE, QEH, QFP, QNR, QNRH, QP, QPH, QF, QT, QPF (GFCI), QSAP (Surge Protector), HQP
Cutler-Hammer/Westinghouse Series BD, BR, BQ, GFC
Square D Series HOM*
GE Series THQL, THHQL (60 amp maximum)
*NOTE: Square D HOM series branch circuit breakers cannot be installed in the top right position on Models ATS2001D and
ATS2001R. If you are planning to use Square D branch circuit breakers, please install them in other positions on the bus.