HP (Hewlett-Packard) 545740-002 Server User Manual


 
Figure 3-2 North America/Japan Power Setup
International Power Setup With Rack-Mounted UPS
To setup the power feed connections as shown in Figure 3-3 (page 41):
1. Connect one 3-phase 32A power feed to the rack-mounted UPS IEC309 532P6 (32A, 5 wire/4
pole) input connector.
2. Connect one 3-phase 16A power feed to the AF508A PDU IEC309 516P6 (16A, 5 wire/4 pole)
input connector.
3. Connect one 3-phase 16A power feed to the c7000 enclosure's IEC309 516P6 (16A, 5 wire/4
pole) input connector.
40 System Installation Specifications