HP (Hewlett-Packard) 545740-002 Server User Manual


 
One c7000 enclosure with 8 NonStop Server Blades
Two IP or Storage CLIMs
Two SAS disk enclosures
One IOAM enclosure
Two Fibre channel disk modules
One rack-mounted system console with keyboard/monitor units
One maintenance switch
One 42U high cabinet
For a total thermal load for a system with multiple cabinets, add the heat outputs for all the
cabinets in the system.
Table 3-1 Example of Cabinet Load Calculations
BTU/hour
2
Total Volt-amps (VA)
1
WeightHeight
(U)
QuantityComponent
AC line(s) poweredAC line(s) powered(kg)(lbs)
BothSingleBothSingle
137001240044004300218480101c7000 enclosure
247221407406405412042IP or Storage
CLIM
18721738560520509642SAS disk
enclosure
1112893326262106235111IOAM
enclosure
237419806965807015662Fibre Channel
disk module
696696204204153421Rack-mounted
System Console
(includes
keyboard and
monitor)
15015044443611Maint. switch
----137303421Cabinet
223761999769706550653143038-Total
1 Decrease the apparent power VA specification by 508VA for each empty NonStop Server Blade slot. For example,
a c7000 that only has four NonStop Server Blades installed would be rated 4400 VA minus (4 server blades x 508
VA) = 2370 VA apparent power.
2 Decrease the BTU/hour specification by 1730 BTU/hour for each empty NonStop Server Blade slot. For example, a
c7000 that only has four NonStop Server Blades installed would be rated 13700 BTU/hour minus (4 server blades x
1730 BTU/hour) = 6780 BTU/hour.
52 System Installation Specifications