In cabinets without the optional rack-mounted UPS, each of the two PDUs requires a separate
branch circuit of these ratings:
Amps (see following “CAUTION”)VoltsRegion
30208North America and Japan
16
1
400International
1 Category D circuit breaker is required.
CAUTION: Be sure the hardware configuration and resultant power loads of each cabinet within
the system do not exceed the capacity of the branch circuit according to applicable electrical
codes and regulations.
Branch circuit requirements vary by the input voltage and the local codes and applicable
regulations regarding maximum circuit and total distribution loading.
Select circuit breaker ratings according to local codes and any applicable regulations for the
circuit capacity. Note that circuit breaker ratings vary if your system includes the optional
rack-mounted HP Model R12000/3 Integrated UPS.
These ratings apply to systems with the optional rack-mounted HP Model R12000/3 Integrated
UPS:
UPS Input Rating
1
Input PlugPower Out (VA/Watts)Operating Voltage
Settings
Version
Dedicated 36 AmpIEC-309 60 Amp12000208North America and
Japan
Dedicated 24 AmpIEC-309 32 Amp12000230International
1 The UPS input requires a dedicated (unshared) branch circuit that is suitably rated for your specific UPS.
For further information and specifications on the R12000/3 UPS (12kVA model), refer to the HP
3 Phase UPS User Guide for the 12kVA model. This guide is available at:
http://bizsupport.austin.hp.com/bc/docs/support/SupportManual/c01079392/c01079392.pdf
Enclosure AC Input
Enclosures (c7000, IP CLIM, IOAM enclosure, and so forth) require:
ValueSpecification
200/208/220/230/240 V AC RMSNominal input voltage
180-264 V ACVoltage range*
50 or 60 HzNominal line frequency
47-53 Hz or 57-63 HzFrequency ranges
3Number of phases (c7000 enclosure only)
1Number of phases (all other components)
Phase Load Balancing
Each PDU is wired such that there are three load segments with groups of outlets alternating
between load segments, going up and down the PDU. Refer to “Power Distribution Units (PDUs)”
(page 42). Factory-installed enclosures, other than the c7000, are connected to the PDUs on
alternating load segments to facilitate phase load balancing. The c7000 has its own three-phase
AC Input Power for Modular Cabinets 45