AI232 Commands: alarm
8-20
alarm
Description
This command:
z Displays a list of the alarm groups and the overall alarm severity
z Displays alarms for a specified alarm group or for a specified range of severity
levels within an alarm group
z Displays alarms by severity level or for a specified range of severity levels
z Clears all non-self-clearing alarm groups and the overall alarm severity
z Clears a specified non-self-clearing alarm group
z Masks a specified alarm group
z Unmasks a specified alarm group.
Command Type
shell
Formats
alarm [
group
[
range
] ]
alarm -sev [
range
]
alarm { -clear [
group
] | -mask
group
| -unmask
group
}
Parameters
group
Defines the group of alarms to display, clear, mask, or unmask. Valid
values are existing alarm groups.
range
Defines a range of alarm severity levels to display. Valid values are 1 to
32. Individual values in the range are separated by hyphens (-).
-sev
Displays all alarms or a range of alarms based severity level.
-clear
Clears all non-self-clearing alarm groups or a specified non-self-clearing
alarm group.
Note: Only non-self-clearing alarm groups can be manually cleared.
Self-clearing alarms clear themselves when the problem that
caused the alarm is resolved.
-mask
Prevents a specified alarm group from affecting overall alarm severity.
-unmask
Allows a specified alarm group to affect overall alarm severity.