64 Preparing for installation
General inspections
General inspections ensure that the following conditions are
met
-
building cross-connect terminals are provided
-
conduits or floor ducts to terminal locations are‘installed (including
service fittings)
-
access conduit for raceway is in place
-
sufficient terminal blocks are provided
-
sufficient cross-connect
yire
is provided
Reserve power inspections
For reserve power inspections if batteries are used, ensure that the following
conditions are
metz
-
reserve power room is well ventilated and operating at optimum
temperature (specific gravity readings are based on a temperature of 77”
F (25” C)
-
proper lighting is available
-
reserve power room is located within manufacturer’s recommended
proximity to the switch
-
protective equipment is available (goggles, face shields, acid-resistant
gloves, protective aprons, water for rinsing eyes/skin, and bicarbonate
sew
-
reserve power room is well secured
-
floor loading requirements are met
-
reserve power room is accessible (no blocking of doorway)
-
noise levels meet OSHA standards 1910.5 or local standards
internationally
-
reserve power area properly interfaces to the equipment
Note:
For detailed instructions on battery usage, see ANSI/IEEE
Standard 450-1987: “IEEE Recommended Practive for Maintenance,
Testing, and Replacement of Large Lead Storage Batteries for
Generating Stations and Substations.”
Installation planning 553-3001-120