Omron CS1W-ETN11 Network Card User Manual


 
273
CPU Bus Unit Allocations in the CPU Unit Appendix F
Internode Test Response Monitoring Time (CPU Unit to Ethernet Unit)
Internode Test Status (Ethernet Unit to CPU Unit)
Number of Internode Test Runs (Ethernet Unit to CPU Unit)
Number of Internode Test Timeout Errors (Ethernet Unit to CPU Unit)
Number of Internode Test Response Errors (Ethernet Unit to CPU Unit)
Number of Internode Test Transmission Errors (Ethernet Unit to CPU Unit)
Number of Times Internode Test Data Did Not Match (Ethernet Unit to CPU Unit)
TCP Socket No. (1 to 8) Connection Status (Ethernet Unit to CPU Unit)
Mail Status (Ethernet Unit to CPU Unit)
Response monitoring time (0000 to FFFF Hex)
(2 seconds when set to 2 seconds)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
m+2
Timeout
Response error
Send error
Data does not match
Routing table error
Send parameter error
Error code
15 14 13 12 11 10 9 8 7 6 5 4 3 2 10
m+3
Number of test runs (0000 to FFFF Hex)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
m+4
Number of timeout errors (0000 to FFFF)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
m+5
Number of response errors (0000 to FFFF)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
m+6
Number of transmission errors (0000 to FFFFHex)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
m+7
Number of data disagreement errors (0000 to FFFF)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
m+8
TCP connection status
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
m+9 to m+16
User mail status
Periodic mail status
Error log mail status
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
m+17