Omron CS/CJ Series Network Card User Manual


 
66
CPU Bus Unit System Setup Section 4-2
If none of these types of data is selected, mail will not be sent even if the set-
ting is made for mail to be sent whenever an error is registered.
Mail Interval
When mail is sent periodically, it is sent at the time interval that is set here.
The setting range is 1 to 1,440, in units of 10 seconds, so the mail can be sent
at intervals of from once every 10 seconds to once every 10 days. This setting
is only enabled when the periodic mail setting (see above) is selected.
If the mail interval is set to 0, then mail will not be sent periodically. If it is set to
a value greater than 1,440, it will be processed as 1,440 (10 days).
The default setting is 0 (mail not sent periodically).
Periodic Mail for User Data
Specify whether or not user data is to be added to mail contents when mail is
sent periodically. The user data is ASCII data stored with the CPU Unit’s I/O
memory address set for the mail function’s “user-created mail data address”
at the beginning. (When user data is sent, 1,024 bytes or the data up to the
null code (00 Hex) is transmitted.)
Periodic Mail for Error Log Information
Specify whether or not all error log information (64 records max.) is to be
added to mail contents when mail is sent periodically.
Periodic Mail for Status Information
Specify whether or not status information is to be added to mail contents
when mail is sent periodically.
User-created Mail Data
Address
Specify, by area classification and beginning word address, the CPU Unit’s
memory address for the data (user-created information) to be transmitted
when data is sent by user request. The default setting is for no address to be
set.
Local Mail Address In 50 or fewer characters, specify the mail address to be entered in the “From”
field in the mail.
Destination Mail Address In 50 or fewer characters, specify the address to which the mail is to be sent.
SMTP Server Address Specify the IP address of the mail server (i.e., the SMTP server address). The
setting range is 0.0.0.0 to 255.255.255.255. The default is 0.0.0.0 (nothing
set).
Setting Meaning
Not selected (Default) Mail is not sent periodically.
Selected Mail is sent periodically.
Setting Meaning
Not selected (Default) User data not included in periodic mail.
Selected User data included in periodic mail.
Setting Meaning
Not selected (Default) Error log information not included in periodic mail.
Selected Error log information included in periodic mail.
Setting Meaning
Not selected (Default) Status information not included in periodic mail.
Selected Status information included in periodic mail.