Powerware 208/120V Power Supply User Manual


 
INSTALLATION
EATON Powerware
®
Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com
30
11. Click the Feature Settings tab to display the EMS Feature Settings
page.
12. Configure the following Miscellaneous Features:
Feature Setting Description
Audible Horn Disabled Select to disable the audible horn. If enabled, the horn
sounds for each new alarm and can be turned off by
pressing any key on the display.
Meter Simulation Mode
Enabled
Select to enable demonstration mode for use with a
simulator.
LCD Displays Input 1 V as L to L
LCD Displays Input 2 V as L to L
Select to display Line to Line voltages on the display.
If unselected, voltages display as Line to Neutral
voltages.
Enable THD Alarms Select to enable Total Harmonic Distortion metering
alarms detected by monitor.
Enable Dual Input Mode Select for dual input models.
NOTE Deselecting this option removes all selections
and displays for the second input.
13. Configure the following Building Alarm Settings:
Feature Setting Description
Set Custom Alarm Name Type a name for Building Alarms 1 through 4.
Contact Type Select if the Building Alarm is connected as
normally−closed.
Action When Active Select the action to occur when the Building Alarm
becomes active.
NOTE To revert any changes made on the current page back to default settings before
saving, click
Reload Config.
14. Click Save Config to save the settings to the EMS−UGK. Depending
on communication speed, updates take effect within 15–20
seconds.