Powerware 208/120V Power Supply User Manual


 
INTRODUCTION
EATON Powerware
®
Energy Management System (EMS) Upgrade Kit User’s Guide S 164201724 Rev 1 www.powerware.com
2
The following options for the EMS−UGK are available:
S Single panel (42 circuits) or dual panel (84 circuits)
S 208/120V or 380/220V, 400/230V, 415/240V rating
S Liquid crystal display (LCD) for local indication of energy usage
S Conduit box for enhanced harness protection
S Main input monitoring (three phases and one neutral rated to
measure currents up to 400A; up to 100A for input ground)
The following accessories for the EMS−UGK are available:
S Subfeed breaker monitoring, rated to measure currents up to 400A
S 100A branch circuit breaker monitoring
S Temperature and humidity monitoring with the optional
Environmental Monitoring Probe (EMP) that is used with the
Power Xpert Gateway Series 1000 Card installed in the EMS−UGK
The EMS−UGK includes an externally−mounted enclosure with an
optional display. Current transformers (CTs) provide branch circuit
monitoring of installed panelboards. Figure 1 shows an example
installation of an EMS−UGK.
Figure 1. Typical EMS−UGK Installation (Dual Panel Shown with Optional Display)