Powerware 30-160kVA Power Supply User Manual


 
DESCRIPTION:
DATE:
DRAWING NO:
4of4
INSTALLATION NOTES
SHEET:
REVI SI ON:
C
164201177---1
041500
A --- 5
Po werware 9315 Maintenance Bypass Module 30---160kV A
164201177 Rev. C 041500
Table A--4. Rating and External Wiring Requirements for Powerware 9315
M B M 5 0 --- 1 6 0
KV A, 380:380VAC, 400:400VAC, 415:415VAC
RATING AND EXTERNAL WIRING REQUIREMENT UNITS RATING 50/60 HZ
BASIC UNIT RATING AT
0.8 LAGGING PF LOAD
KVA
KW
160
128
130
104
100
80
80
64
65
52
50
40
40
32
30
24
UPS INPUT VOLTAGE
BYP ASS INPUT/UPS OUTPUT VOLTAGE
VOLTS
VOLTS
380/400/415
380/400/415
A
AC INPUT TO MAINTENANCE BYPASS
(3) PHASES, (1) GROUND
AMPS 231 188 146 115 97 74 60 45
A
CONDUCTOR SIZE
NUMBER PER PHASE
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
1
(1)
1
(1)
1
(1)
B
AC INPUT TO UPS BYPASS
(3) PHASES, (1) GROUND
AMPS 231 188 146 115 97 74 60 45
B
CONDUCTOR SIZE
NUMBER PER PHASE
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
1
(1)
1
(1)
1
(1)
C
AC OUTPUT TO CRITICAL LOAD
(3) PHASES, (1) NEUTRAL, (1) GROUND
AMPS 231 188 146 115 97 74 60 45
C
CONDUCTOR SIZE
NUMBER PER PHASE
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
1
(1)
1
(1)
1
(1)
D
UPS/PTC OUTPUT TO MBM CABINET (MIS)
(3) PHASE, (1) NEUTRAL, (1) GROUND
AMPS 231 188 146 115 97 74 60 45
D
CONDUCTOR SIZE
NUMBER PER PHASE
AWG/MCM
(each)
300
(1)
300
(1)
300
(1)
300
(1)
300
(1)
1
(1)
1
(1)
1
(1)
E
CONTROL WIRING TO UPS
(2) CONDUCTORS
VOLTS
AMPS
120
1
120
1
120
1
120
1
120
1
120
1
120
1
120
1
Note: Callout letters A, B, C, D,and E map to drawing 164201177---4 (Reverse Transfer Connection) and
164201177---7 (Parallel Connection). Read and understand the notes on drawings when planning your installation.