Powerware 30-160kVA Power Supply User Manual


 
A --- 8
Po werware 9315 Maintenance Bypass Module 30-160kVA
164201177 Rev. C 041500
Table C -- 1. Power Cable Terminations
With Optional BIB Without Optional BIB
Terminal
Function
Terminal Function
Size of
Presure
Terminal
Tightening
Torque
N --- M
(lb --- in)
Int.
Hex
Size
(In.)
Size of
Presure
Terminal
Tightening
Torque
N --- M
(lb --- in)
Int.
Hex
Size
(In.)
Powerware 9315
UPS Model in KV A
(see note below)
2 --- #6-350
kcmil
(Note 2)
31.1 (275) 3/8
1 --- #6-350
kcmil
(Note 3)
31.1 (275) 3/8
30---160KVA,
38/38, 48/48, 60/60
30---80KVA, 20/20
AC Input to
MBM
E1,
E2,
E3
Phase A,
Phase B,
Phase C
2 --- #6-350
kcmil
(Note 2)
31.1 (275) 3/8
2 --- #6-350
kcmil
(Note 2)
31.1 (275) 3/8
30---160KVA,
48/20, 60/20
E
3
P
h
a
s
e
C
4 --- #2-600
kcmil
(Note 2)
56.5 (500) 1/2
3 --- #3/0-400
kcmil
(Note 3)
42.4 (375) 5/16 100---160KVA, 20/20
AC Input to
UPS Bypass
(
B
I
B
b
r
e
a
k
e
r
BIB --- 2,
BIB --- 4
,
Phase A,
Phase B
,
1 --- #6-350
kcmil
31.1 (275) 3/8 N/A N/A N/A
30---160KVA,
38/38, 48/48, 60/60, 48/20, 60/20
30---80KVA, 20/20
(BIB breaker
Load side)
B
I
B
-
-
-
4
,
BIB --- 6
P
h
a
s
e
B
,
Phase C
3 --- #3/0-400
kcmil
42.4 (375) 5/16 N/A N/A N/A 100---160KVA, 20/20
UPS Output
to MBM
(
MIS breaker
MIS --- 1,
MIS --- 3,
M
I
S
5
Phase A,
Phase B,
P
h
a
s
e
C
1 --- #6-350
kcmil
311 (275) 3/8
1 --- #6-350
kcmil
311 (275) 3/8
30---160KVA,
38/38, 48/48, 60/60
30---80KVA,
48/20, 60/20, 20/20
(
M
I
S
b
r
e
a
k
e
r
Line side)
MIS --- 5 Phase C
3 --- #3/0-400
kcmil
42.4 (375) 5/16
3 --- #3/0-400
kcmil
42.4 (375) 5/16
100---160KVA,
48/20, 60/20, 20/20
MBM Output
to Critical
L
o
a
d
E13,
E14,
E
1
5
Phase A,
Phase B,
P
h
a
s
e
C
2 --- #6-350
kcmil
31.1 (275) 3/8
2 --- #6-350
kcmil
31.1 (275) 3/8
30---160KVA,
38/38, 48/48, 60/60
30---80KVA,
48/20, 60/20, 20/20
L
oad E15 Phase C
4 --- #2-600
kcmil
56.5 (500) 1/2
4 --- #2-600
kcmil
56.5 (500) 1/2
100---160KVA,
48/20, 60/20, 20/20
Neutral Lug E12 Neutral
12---#2-500
kcmil
56.5 (500) 1/2
12---#2-500
kcmil
56.5 (500) 1/2 30---160KVA, all voltages
Customer
Ground Lug
Ground Ground
2 --- #6-350
kcmil
31.1 (275) 3/8
2 --- #6-350
kcmil
31.1 (275) 3/8 30---160KVA, all voltages
NOTES: Model Number Legend
1. 38/38: 380V AC in---380V AC out; 48/48: 480VAC in---480VAC out; 60/60: 600VAC in---600VAC out
48/20: 480VAC in---208VAC out; 60/20: 600VAC in---208VAC out; 20/20: 208VAC in---208VAC out
2. AC input wiring is connected to input lugs E1---E 3. Lugs are located on the right side of BIB breaker.
3. AC input wiring is connected directly to the line side of MBP breaker (MBP --- 1, MBP --- 3, and MBP --- 5).
4. AC input wiring is connec t ed to input l ugs E1---E3.
DESCRIPTION:
DATE:
DRAWING NO:
1of2
SHEET:
REVI SI ON:
C
041500
164201177---1
INSTALLATION NOTES