Powerware 4500 Power Supply User Manual


 
UPS Operation
51
Powerware
®
9 Prestige SeriesUser’s Guide(4500/6000 VA) Rev H www.powerware.com
Bypass Mode
The indicator and the indicator illuminate simultaneously,
indicating Bypass mode (see Figure 21). When the UPS is in Bypass
mode, the load is powered by utility power. However, utility power
continues to be passively filtered by the UPS.
LOAD ON
UNITON
BYPASS
OVERLOAD
SITE FAULT
OVERTEMP
BATTERY
SELF TEST
Figure 21. Bypass Operation Indicators
Battery Mode
When the UPS is operating during a power outage, the alarm beeps
several times initially, and then once every 10 seconds while in Battery
mode. The
indicator illuminates. The front panel displays the
approximate percentage of battery capacity remaining (see Figure 22).
When the utility power returns, the UPS switches to Normal mode
operation while the battery recharges.
BATTERY
ONLINE
>75%
CAPACITY
REMAINS
BATTERY
ONLINE
>50%
CAPACITY
REMAINS
BATTERY
ONLINE
>25%
CAPACITY
REMAINS
BATTERY
ONLINE
BATTERY
ONLINE
SHUTDOWN
IMMINENT
LOW
BATTERY
WARNING
OVERLOAD
SITE FAULT
OVERTEMP
BATTERY
SELF TEST
Figure 22. Battery Operation Indicators
If battery capacity becomes low while in Battery mode, the Battery Fault
indicator begins to flash and the Self Test indicator remains lit,
indicating approximately two minutes before UPS shutdown. The alarm
beeps every two seconds.