Default SettingsDescriptionLCD MessageParameter
High-Efficiency
Mode
HE Mode Setting Select whether High-Efficiency mode is On or Off. If
enabled, you must also select the input voltage range:
±10% or ±15%.
While operating in High-Efficiency mode, the UPS
transfers to utility power when: 1) the input voltage is
outside ±10% or ±15% from nominal; 2) the input
frequency is greater than ±3%; or 3) the input line is
not available.
You are prompted to save this setting.
HE Mode Off
Free Run Mode Free Run Mode Select whether Free Run mode is On or Off. If enabled,
you must also select Bypass Disable or Bypass Enable.
This selection defines how your UPS runs when the
input frequency (from the utility) is outside the
selected frequency tolerance (set via the I/P F Setting,
above), but is inside the maximum frequency limits the
UPS can accept before switching to Battery mode.
For example: If your 60 Hz UPS is set to the factory
default window of ±5% before the UPS starts
regulating the frequency:
S The output frequency tracks the input frequency
exactly from 57 to 63 Hz.
S If input frequency is between 45 and 57 Hz, or
between 63 and 65 Hz, the output frequency is
regulated by the UPS to exactly 60 Hz (±0.5 Hz).
You are prompted to save this setting.
Free Run On
(Bypass Disable)
Alarm Silence Alarm Silence Select whether Silence is On or Off. If enabled, the
UPS silences the alarm for an existing fault. If the UPS
status changes, the alarm beeps, overriding the
previous alarm silencing. The alarm does not silence if
there is a low battery condition.
Silence Off
Manual Battery
Test
Manual Bat Test To initiate a manual battery test, press the button
twice. During the test, the LCD displays
On BATTERY.
The UPS resets the automatic timer after a manual
battery test.
Battery Test
Manual UPS Test Manual UPS Test To initiate a manual UPS self-test, press the button
twice. During the test, the LCD displays
On BATTERY.
UPS Test
Site Wiring Fault
Alarm
Site Fault Set Select Enable or Disable. When enabled, the alarm
sounds when the ground connection is missing or the
line and neutral wires are reversed in the wall outlet.
Detect Enable
Modem Support Modem Support This parameter is reserved for future use, and should
not be modified by the user.
No Modem Support