Powerware 700 3000 VA Network Card User Manual


 
Configuration
20
Powerware
®
9120 User's Guide S 05147426 A Uncontrolled Copy
Default SettingsDescriptionLCD MessageParameter
Number of
Extended Battery
Modules
Bat Pack Num Set Select the number of EBMs connected to the UPS:
S For 700ć1500 VA models, select 0 through 2.
S For 2000ć3000 VA models, select 0 through 5.
You are prompted to save this setting.
Extern Pack: 0
Communications
Lock-out
COM Control Cmds For greater levels of security, users may choose to
have the UPS disregard shutdown commands that
come from the power management software or other
communication sources.
S When disabled, the UPS does not accept a shut
down command via the communication port, USB
port, or communication slot adapter.
S When enabled, the UPS operates normally in
response to external commands.
You are prompted to save this setting.
Enable
Load Segment
Control
Load Group Set Allows manual control of load segments (see Load
Segments" on page 24).
By repeatedly pressing the scroll button, the individual
load segments can be turned on and off.
CAUTION To prevent the unintentional shutdown of
specific load segments, confirm your selection before
pressing the button.
Group 1On 2On
Manual Bypass Manual Bypass GO This parameter is used to manually place the UPS in
Bypass mode.
Bypass OFF
Configuration Mode
Setting
Config Mode Set This parameter is reserved for future use, and should
not be modified by the user. The setting may be
toggled between
EscapeConfigMode and Enter
ConfigMode. It should always be set to
EscapeConfigMode.
EscapeConfigMode