Powerware Powerware 9390 Network Card User Manual


 
POWER WIRING INSTALLATION NOTES
092107
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
D
164201546---4 6 of 10
INSTALLATION INFORMATION
EATON Powerware
®
9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com
A-22
Table I. UPS Sidecar Maintenance Bypass Power Cable Terminations
80/40, 80/50, 80/60, 80/80, 208/208V and 160/100, 160/120, 160/160, 480/480V
Terminal F unction Function
Size of Pressure
Termination
Tightening Torque
Nm (lb in)
Type
Screw
AC Input to Maintenance
Bypass or Optional BIB
Phase A
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16Hex
3/8Hex
Phase B
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16Hex
3/8Hex
Phase C
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16Hex
3/8Hex
AC Input to Optional RIB
Phase A
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16Hex
3/8Hex
Phase B
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16Hex
3/8Hex
Phase C
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16Hex
3/8Hex
AC Output to Critical Load
Phase A
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16Hex
3/8Hex
Phase B
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16Hex
3/8Hex
Phase C
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16Hex
3/8Hex
Table J. UPS Sidecar 1+1 Parallel Redundant Power Cable Terminations
40/20, 40/30, 40/40, 208/208V and 80/40, 80/50, 80/60, 80/80, 480/480V
Terminal F unction Function
Size of Pressure
Termination
Tightening Torque
Nm (lb in)
Type
Screw
AC Input from UPM2 to
MOB 2 (standalone
installation)
Phase A 1 --- #4 --- 350 kcm il
20.3 (180)
3/16Hex
Phase B 1 --- #4 --- 350 kcm il
20.3 (180)
3/16Hex
Phase C 1 --- #4 --- 350 kcmil
20.3 (180)
3/16Hex
AC Output to Critical Load
(without SLB) Terminal
Block
Phase A 1 --- #14 --- 2/0
13.5 (120)
3/16Hex
Phase B 1 --- #14 --- 2/0
13.5 (120)
3/16Hex
Phase C 1 --- #14 --- 2/0
13.5 (120)
3/16Hex
AC Output to Critical Load
(with SLB)
Phase A 1 --- #4 --- 350 kcm il
20.3 (180)
3/16Hex
Phase B 1 --- #4 --- 350 kcm il
20.3 (180)
3/16Hex
Phase C 1 --- #4 --- 350 kcmil
20.3 (180)
3/16Hex
Neutral (80/480) Neutral 4 --- #14 --- 1/0 5.6 (50) Slotted
Neutral (40/208) Neutral 8 --- #6 --- 250 kcm il 42.4 (375) 5/16Hex
Ground Ground 2 --- #14 --- 1/ 0 5.6 (50) Slotted