9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com
A-24
Table M. UPS Sidecar 1+1 Parallel Redundant Power Cable Terminations
160/100, 160/120, 160/160 kVA 480/480V
Terminal F unction Function
Size of Pressure
Termination
Tightening Torque
Nm (lb in)
Type
Screw
AC Input from UPM2 to
MOB 2 (standalone
installation)
Phase A
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16Hex
3/8Hex
Phase B
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16Hex
3/8Hex
Phase C
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16Hex
3/8Hex
AC Output to Critical Load
(without SLB)
Phase A
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16Hex
3/8Hex
Phase B
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16Hex
3/8Hex
Phase C
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16Hex
3/8Hex
AC Output to Critical Load
(with SLB)
Phase A
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16Hex
3/8Hex
Phase B
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16Hex
3/8Hex
Phase C
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16Hex
3/8Hex
Neutral Neutral 8 --- #6 --- 250 kcm il 42.4 (375) 5/16Hex
Ground Ground 4 --- #14 --- 1/ 0 5.6 (50) Slotted
TableN.UPSSidecar1+1ParallelRedundantPowerCableTerminations
40/20, 40/30, 40/40 kVA 480/480V
Terminal F unction Function
Size of Pressure
Termination
Tightening Torque
Nm (lb in)
Type
Screw
AC Input from UPM2 to
MOB 2 (standalone
installation)
Phase A 1 --- #14 --- 3/0
5.6 (50)
Slotted
Phase B 1 --- #14 --- 3/0
5.6 (50)
Slotted
Phase C 1 --- #14 --- 3/0
5.6 (50)
Slotted
AC Output to Critical Load
(without SLB) Terminal
Block
Phase A 1 --- #14 --- 2/0 13.5 (120) 3/16Hex
Phase B 1 --- #14 --- 2/0 13.5 (120) 3/16Hex
Phase C 1 --- #14 --- 2/0 13.5 ( 120) 3/16Hex
AC Output to Critical Load
(with SLB)
Phase A 1 --- #14 --- 3/0 5.6 (50) Slotted
Phase B 1 --- #14 --- 3/0 5.6 (50) Slotted
Phase C 1 --- #14 --- 3/0 5.6 (50) Slotted
Neutral Neutral 4 --- #14 --- 1/0 5.6(50) Slotted
Ground Ground 2 --- #14 --- 1/ 0 5.6 (50) Slotted