TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R (2) AV 38 ALARM_3 System Alarm #3
R (2) AV 39 ALARM_4 System Alarm #4
R (2) AV 40 ALARM_5 System Alarm #5
R (2) AV 41 E_C1_ACM_HRS Elite Compressor #1 Accumulated Run Time
(in hours)
R (2) AV 42 E_C2_ACM_HRS Elite Compressor #2 Accumulated Run Time
(in hours)
R (2) AV 43 E_C3_ACM_HRS Elite Compressor #3 Accumulated Run Time
(in hours)
R (2) AV 44 E_C4_ACM_HRS Elite Compressor #4 Accumulated Run Time
(in hours)
R (2) AV 45 I_C1_ACM_HRS Intelli-Comfort Compressor #1 Accumulated
Run Time (in hours)
R (2) AV 46 I_C2_ACM_HRS Intelli-Comfort Compressor #2 Accumulated
Run Time (in hours)
R (2) AV 47 HGR_VLV_OUT Hot Gas Reheat Valve Output Status
(0-100%)
R (2) AV 48 NUMBER_HEAT Number of Heat Stages Available
R (2) AV 49 OP_HEAT_STPT 68 45 99 Operating Heating Setpoint
R/W (2) AV 50 OCC_HEAT_SP 68 45 99 Occupied Heating Setpoint
R/W (2) AV 51 UNOC_HEAT_SP 60 45 99 Un-Occupied Heating Setpoint
R/W (2) AV 52 SAT_HEAT_SP 135 100 180 Supply Air Temperature Limit for Heating
Setpoint (degrees F)
R/W (2) AV 53 SAT_ALM_HEAT 0 0 120 Supply Air Temperature Alarm Setpoint for
Heating
R/W (2) AV 54 OAT_HEAT_L_O 75 0 100 Outdoor Air Temperature HeatingLockout
Temperature
R (2) AV 55 HW_VLV_OUT Hot Water Valve Output Status (0-100%)
R (2) AV 56 CV_VAV_SELEC CV/VAV Selected (0= Valid CV, 1=Valid VAV,
2= Invalid Value)
R/W (2) AV 57 BLDG_SP_STPT 0.1 -0.25 0.25 Building Static Pressure Setpoint
R/W (2) AV 58 DUCT_SP_STPT 1.5 0 5 Duct Static Pressure Setpoint
R/W (2) AV 59 DUCT_SD_STPT 4.5 0 5 Duct Static Pressure Shutdown Setpoint
R/W (2) AV 60 VAV_OHEAT_SP 68 40 85 VAV Occupied Heating Setpoint (degrees F)
R/W (2) AV 61 MWU_RAT_STPT 70 50 85 Morning Warm-Up and VAV Heating: Return
Air Temperature Setpoint (degrees F)
R/W (2) AV 62 HYD_S1_SA_SP 120 80 180 Hydronic Heating Stage #1 Supply Air
Setpoint (degrees F)
R/W (2) AV 63 HYD_S2_SA_SP 150 80 180 Hydronic Heating Stage #2 Supply Air
Setpoint (degrees F)
R/W (2) AV 64 VAV_CL_HI_SP 60 40 70 VAV Cooling Supply Air Temperature: Upper
Setpoint (degrees F)
R/W (2) AV 65 VAV_CL_LO_SP 55 40 70 VAV Cooling Supply Air Temperature: Lower
Setpoint (degrees F)
R/W (2) AV 66 VAV_SAT_RSET 72 40 85 VAV Cooling Supply Air Temperature: Reset
Setpoint (Space Temperature) (degrees F)
R (2) AV 67 REVISION 0 0 xx Device Revision