TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R (5) BV 19 LOW_AMB_OVRD Low Ambient Temperature (0=comps not
overridden by LAT, 1=comps overridden)
R (5) BV 20 POP_ENABLED Pre-Occupancy Purge Enabled
R (5) BV 21 FAN_ON_W_SEN CV - Indoor Fan Operates with Space
Sensor Present Option Enabled
R (5) BV 22 SAT_COOLING Supply Air Temperature Limit for Cooling
Enabled
R (5) BV 23 COOLING_ENA Cooling Mode Enabled
R (5) BV 24 SAT_HEATING Supply Air Temperature Limit for Heating
Enabled
R (5) BV 25 HEATING_ENA Heating Mode Enabled
R (5) BV 26 SEN_FAULT_EN Space Sensor Fault Override (Construction
Mode) Enabled
R (5) BV 28 INTELLI-STRT Intelli-Start Enabled
R (5) BV 29 BP_SENS_INST Building Static Pressure Sensor Installed
R (5) BV 30 EX_FAN_STAT Exhaust Fan Output Status (0=output is OFF,
1=output is ON)
R (5) BV 31 ECONO_STATUS Economizer Output Status (0=not Free
Cooling, 1= Free Cooling)
R (5) BV 32 FRECOOL_STAT Free Cooling Mode Status (0=comps not
overridden by Econo, 1=comps overridden)
R (5) BV 33 COM_VENT_STA Comfort Ventilation Mode Status (1=control
is in Comfort Vent mode, 0= it is not)
R (5) BV 34 CVM_COOLING Comfort Ventilation Mode for Cooling
Enabled
R (5) BV 35 CVM_HEATING Comfort Ventilation Mode for Heating
Enabled
R (5) BV 36 ECO_L_TO_SAT Economizer Loading to Control Supply Air
Temperature Enabled
R (5) BV 37 OAH_SENSOR Outside Air Humidity Sensor Enabled
R (5) BV 38 RAH_SENSOR Return/Inside Air Humidity Sensor Enabled
R (5) BV 39 DEMAND_VENT Demand Ventilation (using Inside Sensor)
Enabled
R (5) BV 40 E_IFAN_STAT Elite Indoor Fan Output Status (0=output is
OFF, 1=output is ON)
R (5) BV 41 E_FAN_ OVER Elite Fan Overload Switch Input Status
(1=closed, 0=open/fault)
R (5) BV 42 E_COMP1_STAT Elite Compressor #1 Output Status (0=output
is OFF, 1=output is ON)
R (5) BV 43 E_LPS1 Elite Low Pressure Switch for Compressor
#1 Input Status (1=closed, 0=open/fault)
R (5) BV 44 E_HPS1 Elite High Pressure Switch for Compressor
#1 Input Status (1=closed, 0=open/fault)
R (5) BV 45 E_C1_OVRLOAD Elite Compressor #1 Overload Switch Input
Status (1=closed, 0=open/fault)
R (5) BV 46 E_COMP2_STAT Elite Compressor #2 Output Status (0=output
is OFF, 1=output is ON)