TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R (5) BV 47 E_LPS2 Elite Low Pressure Switch for Compressor
#2 Input Status (1=closed, 0=open/fault)
R (5) BV 48 E_HPS2 Elite High Pressure Switch for Compressor
#2 Input Status (1=closed, 0=open/fault)
R (5) BV 49 E_C2_OVRLOAD Elite Compressor #2 Overload Switch Input
Status (1=closed, 0=open/fault)
R (5) BV 50 E_CFAN1_STAT Elite Condenser Fan #1 Output Status
(0=output is OFF, 1=output is ON)
R (5) BV 51 E_COMP3_STAT Elite Compressor #3 Output Status (0=output
is OFF, 1=output is ON)
R (5) BV 52 E_LPS3 Elite Low Pressure Switch for Compressor
#3 Input Status (1=closed, 0=open/fault)
R (5) BV 53 E_HPS3 Elite High Pressure Switch for Compressor
#3 Input Status (1=closed, 0=open/fault)
R (5) BV 54 E_C3_OVRLOAD Elite Compressor #3 Overload Switch Input
Status (1=closed, 0=open/fault)
R (5) BV 55 E_COMP4_STAT Elite Compressor #4 Output Status (0=output
is OFF, 1=output is ON)
R (5) BV 56 E_LPS4 Elite Low Pressure Switch for Compressor
#4 Input Status (1=closed, 0=open/fault)
R (5) BV 57 E_HPS4 Elite High Pressure Switch for Compressor
#4 Input Status (1=closed, 0=open/fault)
R (5) BV 58 E_C4_OVRLOAD Elite Compressor #4 Overload Switch Input
Status (1=closed, 0=open/fault)
R (5) BV 59 E_CFAN2_STAT Elite Condenser Fan #2 Output Status Input
Status (0=output is OFF, 1=output is ON)
R (5) BV 60 E_GAS_VLVE1 Elite Gas Valve #1 Input Status
(1=energized, 0=not energized)
R (5) BV 61 E_LIMIT_ 1 Elite Limit Switch #1 Input Status (1=closed,
0=open/fault)
R (5) BV 62 E_GAS_VLVE2 Elite Gas Valve #2 Input Status
(1=energized, 0=not energized)
R (5) BV 63 E_LIMIT_ 2 Elite Limit Switch #2 Input Status (1=closed,
0=open/fault)
R (5) BV 64 E_GAS_VLVE3 Elite Gas Valve #3 Input Status
(1=energized, 0=not energized)
R (5) BV 65 E_LIMIT_ 3 Elite Limit Switch #3 Input Status (1=closed,
0=open/fault)
R (5) BV 66 E_FREEZE_ST Hot H2O Freeze Thermostat Switch #1 Input
Status (1=closed, 0=open/fault)
R (5) BV 67 FAN_HEAT Turn OFF Continuous Fan when Starting
Heat Enabled (0=Continuous Fan ON)
R (5) BV 68 HEAT_1_STAT H1 Heating Output #1 Status (0=output is
OFF, 1=output is ON)
R (5) BV 69 HEAT_2_STAT H2 Heating Output #2 Status (0=output is
OFF, 1=output is ON)
R (5) BV 70 HEAT_3_STAT H3 Heating Output #3 Status (0=output is
OFF, 1=output is ON)