514067-UAD-A-0509
Johnson Controls Unitary Products 9
TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R/W (2) AV 71 SPCE_ALM_TMP 0 0 25 Space Sensor Alarm Temperature (degrees
F, 0 = disabled)
R/W (2) AV 72 SPCE_ALM_TIM 0 0 120 Space Sensor Alarm Time (minutes F, 0 =
disabled)
R (5) BV 26 SEN_FAULT_EN – – – Space Sensor Fault Override (Construction
Mode) Enabled
R/W (2) AV 73 SP_OFF_RANGE 3 0 5 Space Temprature Sensor Offset Range
(0-5 degrees)
R (2) AV 4 SUP_AIR_TEMP – – – Supply Air Temperature
R/W (2) AV 70 SAT_ALM_COOL 0 0 80 Supply Air Temperature Alarm Setpoint for
Cooling
R/W (2) AV 53 SAT_ALM_HEAT 0 0 120 Supply Air Temperature Alarm Setpoint for
Heating
R (5) BV 22 SAT_COOLING – – – Supply Air Temperature Limit for Cooling
Enabled
R/W (2) AV 3 SAT_COOL_SP 50 40 65 Supply Air Temperature Limit for Cooling
Setpoint (degrees F)
R (5) BV 24 SAT_HEATING – – – Supply Air Temperature Limit for Heating
Enabled
R/W (2) AV 52 SAT_HEAT_SP 135 100 180 Supply Air Temperature Limit for Heating
Setpoint (degrees F)
R (2) AV 34 SFAN_VFD_OUT – – – Supply Fan VFD Output Status (0-100%)
R (2) AV 36 ALARM_1 – – – System Alarm #1
R (2) AV 37 ALARM_2 – – – System Alarm #2
R (2) AV 38 ALARM_3 – – – System Alarm #3
R (2) AV 39 ALARM_4 – – – System Alarm #4
R (2) AV 40 ALARM_5 – – – System Alarm #5
R/W (2) AV 29 TH_OFFSET 5 1 10 Temperature/Humidity % Humidity that =
1°F of Offset
R/W (2) AV 26 TEM_HUM_STPT 50 20 80 Temperature/Humidity Setpoint (percent
Humidity)
R (5) BV 67 FAN_HEAT – – – Turn OFF Continuous Fan when Starting
Heat Enabled (0=Continuous Fan ON)
R/W (2) AV 2 UNOC_COOL_SP 85 45 99 Un-Occupied Cooling Setpoint
R/W (2) AV 51 UNOC_HEAT_SP 60 45 99 Un-Occupied Heating Setpoint
R/W (2) AV 75 UNOC_OVR_TP 60 0 240 Unoccupied Override Time Period
R/W (2) AV 65 VAV_CL_LO_SP 55 40 70 VAV Cooling Supply Air Temperature: Lower
Setpoint (degrees F)
R/W (2) AV 66 VAV_SAT_RSET 72 40 85 VAV Cooling Supply Air Temperature: Reset
Setpoint (Space Temperature)(degrees F)
R/W (2) AV 64 VAV_CL_HI_SP 60 40 70 VAV Cooling Supply Air Temperature: Upper
Setpoint (degrees F)
R (5) BV 5 VAV_OCC_HEAT – – – VAV Occupied Heating Enabled
R/W (2) AV 60 VAV_OHEAT_SP 68 40 85 VAV Occupied Heating Setpoint (degrees F)