Simplicity 514067-UAD-A-0509 Network Router User Manual


 
514067-UAD-A-0509
Johnson Controls Unitary Products 7
TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R (5) BV 66 E_FREEZE_ST Hot H2O Freeze Thermostat Switch #1
Input Status (1=closed, 0=open/fault)
R (2) AV 55 HW_VLV_OUT Hot Water Valve Output Status (0-100%)
R (5) BV 2 HYDRONC_HEAT Hydronic Heat Enabled
R (5) BV 3 HH_REVER_VLV Hydronic Heat Reverse Actuated Valve
Installed
R/W (2) AV 62 HYD_S1_SA_SP 120 80 180 Hydronic Heating Stage #1 Supply Air
Setpoint (degrees F)
R/W (2) AV 63 HYD_S2_SA_SP 150 80 180 Hydronic Heating Stage #2 Supply Air
Setpoint (degrees F)
R/W (2) AV 80 IO_DVNT_STPT 700 0 2000 Indoor/Outdoor Demand Ventilation
Setpoint
R (2) AV 45 I_C1_ACM_HRS Intelli-Comfort Compressor #1 Accumulated
Run Time (in hours)
R (5) BV 73 I_COMP1_STAT Intelli-Comfort Compressor #1 Input Status
(0=output is OFF, 1=output is ON)
R (2) AV 46 I_C2_ACM_HRS Intelli-Comfort Compressor #2 Accumulated
Run Time (in hours)
R (5) BV 76 I_COMP2_STAT Intelli-Comfort Compressor #2 Input Status
(0=output is OFF, 1=output is ON)
R (5) BV 79 I_CFAN_STAT Intelli-Comfort Condenser Fan #1 Input
Status (0=output is OFF, 1=output is ON)
R (5) BV 72 I_FAN_OVER Intelli-Comfort Fan Overload Switch Input
Status (0=open,1=closed)
R (5) BV 82 I_FREEZE_1 Intelli-Comfort Freeze Thermostat Switch #1
Input Status (0=open,1=closed)
R (5) BV 83 I_FREEZE_2 Intelli-Comfort Freeze Thermostat Switch #2
Input Status (0=open,1=closed)
R (5) BV 80 I_GAS_VLVE1 Intelli-Comfort Gas Valve #1 Input Status
R (5) BV 75 I_HPS1 Intelli-Comfort High Pressure Switch for
Compressor #1 Input Status (1=closed,
0=open/fault)
R (5) BV 78 I_HPS2 Intelli-Comfort High Pressure Switch for
Compressor #2 Input Status (1=closed,
0=open/fault)
R (5) BV 71 I_IFAN_STAT Intelli-Comfort Indoor Fan Output Status
(0=output is OFF, 1=output is ON)
R (5) BV 81 I_LIMIT_1 Intelli-Comfort Limit Switch #1 Input Status
R (5) BV 74 I_LPS1 Intelli-Comfort Low Pressure Switch for
Compressor #1 Input Status (1=closed,
0=open/fault)
R (5) BV 77 I_LPS2 Intelli-Comfort Low Pressure Switch for
Compressor #2 Input Status (1=closed,
0=open/fault)
R (5) BV 28 INTELLI-STRT Intelli-Start Enabled
R/W (5) BV 13 LOADSHED Loadshed (0=clear loadshed, 1=set load-
shed operation)
R (5) BV 19 LOW_AMB_OVRD Low Ambient Temperature (0=comps not
overridden by LAT, 1=comps overridden)