Simplicity 514067-UAD-A-0509 Network Router User Manual


 
514067-UAD-A-0509
16 Johnson Controls Unitary Products
TROUBLESHOOTING
The Simplicity
®
LINC Gateway consists of two printed circuit
boards.
TABLE 4: SIMPLICITY
®
LINC GATEWAY
RS485 BOARD (Bottom) BacNET Board (Top)
Normal Board Operation Normal Board Operation
The PWR LED should be on during operation. The RX and TX
LEDs should flash when a signal is either received or sent.
LEDs LA and LB flash about once per second. LED GP105 will
remain on within 45-60 seconds after power up, signifying normal
operation. The PWR LED should be on during operation. The RX
and TX LEDs should flash when a signal is either received or
sent.
Faulty Board Operation Faulty Board Operation
If the PWR LED does not come on but the RX and TX flash, then
the PWR LED is broken.
If the PWR LED does not come on but the RX and TX flash, then
the PWR LED is broken.
If the TX and / or RX LEDs do not flash, it may represent a problem
with the field wiring or configuration problems in the field side of
the BacNET board. It may also indicate incorrect polling
parameters such as baud rate or parity.
If the TX and / or RX LEDs do not flash, it may represent a
problem with the field wiring or confguration problems in the field
side of the BacNet board. It may also indicate incorrect polling
parameters such as baud rate or parity.
If the PWR LED does not come on and LA and LB do not flash,
call UP Tech Services at 1-877-874-7378.
If GP105 never comes on, call UP Tech Services at
1-877-874-7378.
General
Power Source 24 ± 15% VAC (Obtained from the Roof Top Unit)
Frequency 45 to 65 HZ
Power Consumption Nominal >2 VA
Operating Environment -40 to 160° F (-40 to 70° C) 10 to 95% non-condensing
Size (H x W x D) 5.0 x 2.4 x 1.8 in. (128 x 61 x 45.75 cm)
Weight 0.2 lb. (0.09 kg)
Processor
Type Microchip
SDRAM Memory 2048 bytes
FLASH Memory 1024 bytes w/1,000,000 write cycle capability
Interface
Port 1 Type BACnet MS/TP
Port 1 Speeds 9.6, 19.2, 38.4, 76.8 kbaud
Port 1 Connector 3-pin screw terminals
Port 2 Type Modbus RTU (RS485)
Port 2 Speeds 9.6, 19,2 kbaud
Port 2 Connector 6-pin screw terminals
LAN Cable Screened Twisted-Pair (Belden 9272 or 89272)
LEDs Controller Status; BACnet; Modbus
Switch Selections MAC Address (1-99), Baud Rate