Simplicity 514067-UAD-A-0509 Network Router User Manual


 
514067-UAD-A-0509
4 Johnson Controls Unitary Products
TABLE 2: POINTS LIST IN DESCRIPTION ORDER
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R (2) AV 14 ACC_OVER_TME Accumulated Unoccupied Override Time
(in hours)
R (2) AV 15 ACTIVE_ALARM Active Alarm
R (5) BV 16 AIR_PROOF_SW Air Proving Switch Status (1=closed,
0=open/no air flow)
R/W (2) AV 79 OAQ_STPT 1000 0 5000 Air Quality Setpoint Outside
R (5) BV 85 ALARM_1_ON Alarm Buffer #1 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 86 ALARM_2_ON Alarm Buffer #2 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 87 ALARM_3_ON Alarm Buffer #3 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 88 ALARM_4_ON Alarm Buffer #4 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 89 ALARM_5_ON Alarm Buffer #5 (0=Alarm has cleared,
1=Alarm is still active)
R (2) AV 33 BLDG_STATIC Building Static Pressure
R (5) BV 29 BP_SENS_INST Building Static Pressure Sensor Installed
R/W (2) AV 57 BLDG_SP_STPT 0.1 -0.25 0.25 Building Static Pressure Setpoint
R/W (2) AV 25 COM_V_LOW_SP 70 60 85 Comfort Ventilation LowerSetpoint
(degrees F)
R (5) BV 34 CVM_COOLING Comfort Ventilation Mode for Cooling
Enabled
R (5) BV 35 CVM_HEATING Comfort Ventilation Mode for Heating
Enabled
R (5) BV 33 COM_VENT_STA Comfort Ventilation Mode Status (1=control
is in Comfort Vent mode, 0= it is not)
R/W (2) AV 24 COM_V_HI_SP 80 60 85 Comfort Ventilation Upper Setpoint
(degrees F)
R (5) BV 23 COOLING_ENA Cooling Mode Enabled
R (5) BV 21 FAN_ON_W_SEN CV - Indoor Fan Operates with Space
Sensor Present Option Enabled
R (2) AV 56 CV_VAV_SELEC CV/VAV Selected (0= Valid CV, 1=Valid
VAV, 2= Invalid Value)
R (2) AV 8 IAQ_VALUE Demand Ventilation (IAQ) Value (PPM)
R (5) BV 39 DEMAND_VENT Demand Ventilation (using Inside Sensor)
Enabled
R/W (2) AV 18 DEMVENT_STPT 1000 0 5000 Demand Ventilation Setpoint
R (2) AV 67 REVISION xx Device Revision
R (5) BV 90 DF_SW_INST Dirty Filter Switch Installed
R (5) BV 15 DIRT_FILT_SW Dirty Filter Switch Status (0=open,1=closed/
fault)
R (2) AV 35 DUCT_STATIC Duct Static Pressure
R/W (2) AV 58 DUCT_SP_STPT 1.5 0 5 Duct Static Pressure Setpoint
R/W (2) AV 59 DUCT_SD_STPT 4.5 0 5 Duct Static Pressure Shutdown Setpoint
R (2) AV 31 ECO_DAMP_OUT Economizer Damper Output Status
(0-100%)