TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R/W (2) AV 69 OP_STPT_DIF 1 1 5 Operating Setpoint Differential
R/W (2) AV 70 SAT_ALM_COOL 0 0 80 Supply Air Temperature Alarm Setpoint for
Cooling
R/W (2) AV 71 SPCE_ALM_TMP 0 0 25 Space Sensor Alarm Temperature
(degrees F, 0 = disabled)
R/W (2) AV 72 SPCE_ALM_TIM 0 0 120 Space Sensor Alarm Time (minutes F,
0 = disabled)
R/W (2) AV 73 SP_OFF_RANGE 3 0 5 Space Temprature Sensor Offset Range
(0-5 degrees)
R/W (2) AV 74 OAT_COOL_L_O 45 0 100 Outdoor Air Temperature Cooling Lockout
Temperature
R/W (2) AV 75 UNOC_OVR_TP 60 0 240 Unoccupied Override Time Period
R (2) AV 76 H1_ACCUM_HRS Heating #1 Accumulated Run Time (in hours)
R (2) AV 77 H2_ACCUM_HRS Heating #2 Accumulated Run Time (in hours)
R (2) AV 78 H3_ACCUM_HRS Heating #3 Accumulated Run Time (in hours)
R/W (2) AV 79 OAQ_STPT 1000 0 5000 Air Quality Setpoint Outside
R/W (2) AV 80 IO_DVNT_STPT 700 0 2000 Indoor/Outdoor Demand Ventilation Setpoint
R/W (2) AV 81 POP_HOURS 4 0 23 Pre-Occupancy Purge Time (hours)
R/W (2) AV 82 POP_MINUTES 0 0 59 Pre-Occupancy Purge Time (minutes)
R/W (2) AV 84 ECON_RAEN_SP 27 10 50 Economizer Return Air Enthalpy Setpoint
R/W (5) BV 1 OCCUPIED_ENA Occupied Enabled
R (5) BV 2 HYDRONC_HEAT Hydronic Heat Enabled
R (5) BV 3 HH_REVER_VLV Hydronic Heat Reverse Actuated Valve
Installed
R (5) BV 4 REM_CONT_ENA Remote Control Enabled
R (5) BV 5 VAV_OCC_HEAT VAV Occupied Heating Enabled
R (5) BV 6 MORN_WARM-UP Morning Warm-Up Enabled
R (5) BV 7 ECONO_INST Economizer Installed
R (5) BV 8 PWR_EX_INST Power Exhaust Installed
R (5) BV 9 MOD_EX_INST Modulating Exhaust Installed
R (5) BV 10 EX_VFD_INST Exhaust VFD Installed
R (5) BV 11 MODBUS_ALARM Modbus Communication Alarm
R/W (5) BV 12 REDLINE Redline (0=clear redline, 1=set redline
operation)
R/W (5) BV 13 LOADSHED Loadshed (0=clear loadshed, 1=set loadshed
operation)
R (5) BV 14 LOW_SUP_VOLT Low Supply Voltage (0=comps not
overridden by LSV, 1=comps overridden)
R (5) BV 15 DIRT_FILT_SW Dirty Filter Switch Status (0=open,1=closed/
fault)
R (5) BV 16 AIR_PROOF_SW Air Proving Switch Status (1=closed,
0=open/no air flow)
R (5) BV 17 PURGE_SWITCH Purge Switch Status (0=open,1=closed)
R (5) BV 18 HGR_STAT Hot Gas Reheat Output Status (0=output is
OFF, 1=output is ON)