Simplicity 514067-UAD-A-0509 Network Router User Manual


 
514067-UAD-A-0509
Johnson Controls Unitary Products 15
TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R (5) BV 71 I_IFAN_STAT Intelli-Comfort Indoor Fan Output Status
(0=output is OFF, 1=output is ON)
R (5) BV 72 I_FAN_OVER Intelli-Comfort Fan Overload Switch Input
Status (0=open,1=closed)
R (5) BV 73 I_COMP1_STAT Intelli-Comfort Compressor #1 Input Status
(0=output is OFF, 1=output is ON)
R (5) BV 74 I_LPS1 Intelli-Comfort Low Pressure Switch for
Compressor #1 Input Status (1=closed,
0=open/fault)
R (5) BV 75 I_HPS1 Intelli-Comfort High Pressure Switch for
Compressor #1 Input Status (1=closed,
0=open/fault)
R (5) BV 76 I_COMP2_STAT Intelli-Comfort Compressor #2 Input Status
(0=output is OFF, 1=output is ON)
R (5) BV 77 I_LPS2 Intelli-Comfort Low Pressure Switch for
Compressor #2 Input Status (1=closed,
0=open/fault)
R (5) BV 78 I_HPS2 Intelli-Comfort High Pressure Switch for
Compressor #2 Input Status (1=closed,
0=open/fault)
R (5) BV 79 I_CFAN_STAT Intelli-Comfort Condenser Fan #1 Input
Status (0=output is OFF, 1=output is ON)
R (5) BV 80 I_GAS_VLVE1 Intelli-Comfort Gas Valve #1 Input Status
R (5) BV 81 I_LIMIT_1 Intelli-Comfort Limit Switch #1 Input Status
R (5) BV 82 I_FREEZE_1 Intelli-Comfort Freeze Thermostat Switch #1
Input Status (0=open,1=closed)
R (5) BV 83 I_FREEZE_2 Intelli-Comfort Freeze Thermostat Switch #2
Input Status (0=open,1=closed)
R (5) BV 85 ALARM_1_ON Alarm Buffer #1 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 86 ALARM_2_ON Alarm Buffer #2 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 87 ALARM_3_ON Alarm Buffer #3 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 88 ALARM_4_ON Alarm Buffer #4 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 89 ALARM_5_ON Alarm Buffer #5 (0=Alarm has cleared,
1=Alarm is still active)
R (5) BV 90 DF_SW_INST Dirty Filter Switch Installed
R (5) BV 93 OCC_COMS_ENA Occupied Thermostat or Communication
Input Enabled
R/W (5) BV 96 MANUAL_WRITE Manual Write Command to ModlINC