Simplicity 514067-UAD-A-0509 Network Router User Manual


 
514067-UAD-A-0509
6 Johnson Controls Unitary Products
TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R (5) BV 44 E_HPS1 Elite High Pressure Switch for Compressor
#1 Input Status (1=closed, 0=open/fault)
R (5) BV 48 E_HPS2 Elite High Pressure Switch for Compressor
#2 Input Status (1=closed, 0=open/fault)
R (5) BV 53 E_HPS3 Elite High Pressure Switch for Compressor
#3 Input Status (1=closed, 0=open/fault)
R (5) BV 57 E_HPS4 Elite High Pressure Switch for Compressor
#4 Input Status (1=closed, 0=open/fault)
R (5) BV 40 E_IFAN_STAT Elite Indoor Fan Output Status (0=output is
OFF, 1=output is ON)
R (5) BV 61 E_LIMIT_ 1 Elite Limit Switch #1 Input Status (1=closed,
0=open/fault)
R (5) BV 63 E_LIMIT_ 2 Elite Limit Switch #2 Input Status (1=closed,
0=open/fault)
R (5) BV 65 E_LIMIT_ 3 Elite Limit Switch #3 Input Status (1=closed,
0=open/fault)
R (5) BV 43 E_LPS1 Elite Low Pressure Switch for Compressor
#1 Input Status (1=closed, 0=open/fault)
R (5) BV 47 E_LPS2 Elite Low Pressure Switch for Compressor
#2 Input Status (1=closed, 0=open/fault)
R (5) BV 52 E_LPS3 Elite Low Pressure Switch for Compressor
#3 Input Status (1=closed, 0=open/fault)
R (5) BV 56 E_LPS4 Elite Low Pressure Switch for Compressor
#4 Input Status (1=closed, 0=open/fault)
R (2) AV 32 EXH_DAMP_OUT Exhaust Damper Output Status (0-100%)
R (5) BV 30 EX_FAN_STAT Exhaust Fan Output Status (0=output is
OFF, 1=output is ON)
R (5) BV 10 EX_VFD_INST Exhaust VFD Installed
R (5) BV 32 FRECOOL_STAT Free Cooling Mode Status (0=comps not
overridden by Econo, 1=comps overridden)
R (5) BV 68 HEAT_1_STAT H1 Heating Output #1 Status (0=output is
OFF, 1=output is ON)
R (5) BV 69 HEAT_2_STAT H2 Heating Output #2 Status (0=output is
OFF, 1=output is ON)
R (5) BV 70 HEAT_3_STAT H3 Heating Output #3 Status (0=output is
OFF, 1=output is ON)
R (2) AV 76 H1_ACCUM_HRS Heating #1 Accumulated Run Time
(in hours)
R (2) AV 77 H2_ACCUM_HRS Heating #2 Accumulated Run Time
(in hours)
R (2) AV 78 H3_ACCUM_HRS Heating #3 Accumulated Run Time
(in hours)
R (5) BV 25 HEATING_ENA Heating Mode Enabled
R/W (2) AV 27 HGR_HUM_STPT 50 0 100 Hot Gas Reheat Humidity Setpoint (percent
Humidity)
R (5) BV 18 HGR_STAT Hot Gas Reheat Output Status (0=output is
OFF, 1=output is ON)
R (2) AV 47 HGR_VLV_OUT Hot Gas Reheat Valve Output Status
(0-100%)