5 Electrical Installation
________________________________________________________________________________________________________________________________________________________________________________________________________________________
52 Product Manual Type: 637f 07-02-10-01-E-V0505.doc
5.6 Fuses, contactors, filters
Compact units
637f/ KD6R 02
.S5
KD6R 04
.S5
KD6R 06
.S5
KD6R 10
.S5
KD6R 16
.S5
KD6R 22
.S5
KD6R 30
.S5
-3 -7 -3 -7 -3 -7 -3 -7 -7 -7 -7
Fuses, Contactors
4)
RCD-switch not recommended. Required setpoint: 300 mA, no protection against life danger
mains input currents [A] 3,5 5 7,5 12 19 26 30
mains protection 1) Type T10A T10A T10A T20A T25A (T32A) 35A (T32A) 35A
protector-switch 2) Type PKZM0-16 PKZM0-16 PKZM0-16 PKZM0-16 PKZM0-25 PKZ2/ZM32 PKZ2/ZM32
mains fuse 2) Type DIL 00M DIL 00M DIL 00M DIL 00M DIL 0M DIL 0M DIL 0M
Line filters
4)
general only for use in earth referenced supplies(TN). Current drain to PE !
single-phase
industrial env.
max. motor cable 50m
(EN55011 A)
Type
LNF E 1*230/012
up to AC 230V !!
+
ferrite core
not possible !
residential env.
max. motor cable 20m
(EN55011 B)
Type
LNF E 1*230/012
up to AC 230V !!
+
ferrite core
not possible !
3-phasig
industrial env.
max. motor cable 50m
(EN55011 A)
Type LNF B 3*480/008
+
ferrite core FR 3
LNF B 3*480/018
+
ferrite core FR 6
LNF B 3*480/033
+
ferrite core FR 6
residential env.
max motor cable 20m
(EN55011 B)
Type LNF B 3*480/008
+
ferrite core FR 3
LNF B 3*480/018
+
ferrite core FR 3
LNF B 3*480/033
+
ferrite core FR 3
3-phasen, max. 3 Units,
supplied by a common filter
industrial env.
max. motor cable 20m
(EN55011 A)
Type LNF B 3*480/018; LNF B *480/033 + ferrite core FR
other types upon request
(according to ref.measurements with 3 units, supplied by common line)
residential env.
max motor cable 20m
(EN55011 B)
3)
Type LNF B 3*480/018; LNF B 3*480/033 + ferrite core FR
other types upon request
(according to ref.measurements with 3 units, supplied by common line)
Plug-in modules
637f / D6R 02
.S5
D6R 04
.S5
D6R 06
.S5
D6R 10
.S5
D6R 16
.S5
D6R 22
.S5
D6R 30
.S5
-3 -7 -3 -7 -3 -7 -3 -7 -3 -7 -3 -7 -3 -7
Fuses, contactors,
filters
4)
1)
general
Orientation: Table for compact units and the addition of rated currents of used
units on the DC-Bus. Depending on the application, energy sharing effects by
DC-link may reduce the required supply current considerable.
fuses
Rule of the thumb: single-phase operation: 2...3 times of added rated currents
Rule of the thumb: 3-phase operation: 1,5...2 times of added rated currents
peak making currents Depending on power-supply unit, limiting equipment is requiered (delay contactor)
filters only for use in earth referenced supplies(TN). Current drain to PE !
filter types Orientation: Table of compact units. Further types: see separate manual
1) recommended for UL-requirements: Bussmann Type FRS-R, 600V, use only UL-approved fuse-holders !
2) recommended, Klöckner Moeller for instance
3) Measurement of conducted emissions only
4) for applications with continuous load: see notes in chapter 5.7