INSTALLING THE VTL VALUE APPLIANCE IN AN EQUIPMENT RACK
2 VTL Value Hardware Installation Guide Aug 2007 A • 316196101
Obtaining required tools, personnel, and materials
1. Make sure that the selected rack meets the following specifications:
The rack has four posts, with a mounting at both front and rear (two-post racks are not
compatible with the VTL Value slide-rails).
The horizontal opening and unit vertical pitch of the rack conform to ANSI/EIA
310-D-1992 or IEC 60927 standards.
The rack’s front and rear rack-mounting planes are 23-34 inches (58-87 cm) apart.
The minimum depth from the rack’s front cabinet door to the front rack-mounting plane is
1.85 inches (4.7 cm).
The minimum depth from the rear cabinet door to the front rack-mounting plane is
38 inches (96.5 cm) with the cable-management arm installed (recommended) or
31.5 inches (80.0 cm) without the cable management arm.
The minimum width between obstructions (such as structural supports and cable troughs)
is 18 inches (45.6 mm) at all points between the front and rear mounting planes.
2. Make sure that the available power meets the requirements listed in the table below:
3. Have the orderable slide-rail assemblies at hand.
4. Have the following tools at hand:
one 10-inch #2 Phillips screwdriver, preferably with a magnetic tip
a carpenter’s spirit level
a mechanical lift (highly recommended).
Caution – The VTL Value appliance weighs 160 pounds (72.7 kg) when fully loaded with
components. To prevent injury to personnel or damage to the equipment, Sun strongly
recommends using a mechanical lift when installing the server in a rack.
5. If a mechanical lift is not available, make sure that at least four trained people are
available to remove the server or reduce the weight of the server by removing
components:
Remove both power supplies.
Remove the system controller.
Location Voltage Amperage Plug type Receptacle type
US/North America: 250 VAC 30 A NEMA L6 30P NEMA L6-30R
EMEA: 230 VAC 32 A IEC-309P IEC-309R