Toshiba ETH-100 Network Router User Manual


 
36
12.4 Exceptions and Troubleshooting
12.4.1 Common Error Causes
Although by no means exhaustive, Table 3 provides possible causes behind
some of the most common errors experienced when using the Modbus TCP/IP
interface.
Table 3: Troubleshooting Reference
Problem Possible Cause
Register addressing is off by 1 Refer to Section 12.3.2 for direct mapping
Modbus TCP/IP client cannot establish
communication with the ETH-100
Ensure at least one of the connected drives is powered on
Check that the drive and Ethernet communication cables are
fully seated into their respective communication ports
Check the Ethernet communication parameters (IP address,
etc.)
Drive does not respond to network
commands / frequency command
Check drive’s frequency mode and command mode selection
parameters
Where applicable, confirm the values of bits #14 and #15 of
communication command word
Confirm that the communication frequency command value is
between lower limit and upper limit frequencies
ILLEGAL FUNCTION exception
(Modbus exception code 01)
The indicated Modbus function is not supported: refer to section 12.2
for a list of supported functions
ILLEGAL DATA ADDRESS exception
(Modbus exception code 02)
The targeted drive register (or one in a group of targeted registers)
does not exist: check the drive’s supported register list
ILLEGAL DATA VALUE exception
(Modbus exception code 03)
The value written was rejected by the drive as invalid: check the value
and drive setting range
NEGATIVE ACKNOWLEDGE
exception (Modbus exception code 07)
An attempt was made to write to a drive register while the drive
was running that does not accept writes while the drive is
running
An attempt was made to write to a read-only register
Confirm that the drive communication cable is fully seated into
the drive’s and ETH-100’s communication ports
Confirm that the drive communication cable is not routed near
the drive’s input power or motor wiring or any other electrical
noise-producing cables or equipment
GATEWAY PATH UNAVAILABLE
exception (Modbus exception code 0A)
Unit Identifier (UI) was invalid: UI must be 1 3
GATEWAY TARGET DEVICE FAILED
TO RESPOND exception (Modbus
exception code 0B)
The targeted drive is not online or failed to respond:
Confirm that the targeted drive is powered-on
Confirm that the drive communication cable is fully seated into
the drive’s and ETH-100’s communication ports
Confirm that the drive communication cable is not routed near
the drive’s input power or motor wiring or any other electrical
noise-producing cables or equipment