12.4 Exceptions and Troubleshooting
12.4.1 Common Error Causes
Although by no means exhaustive, Table 3 provides possible causes behind
some of the most common errors experienced when using the Modbus TCP/IP
interface.
Table 3: Troubleshooting Reference
Problem Possible Cause
Register addressing is off by 1 Refer to Section 12.3.2 for direct mapping
Modbus TCP/IP client cannot establish
communication with the ETH-100
• Ensure at least one of the connected drives is powered on
• Check that the drive and Ethernet communication cables are
fully seated into their respective communication ports
• Check the Ethernet communication parameters (IP address,
etc.)
Drive does not respond to network
commands / frequency command
• Check drive’s frequency mode and command mode selection
parameters
• Where applicable, confirm the values of bits #14 and #15 of
communication command word
• Confirm that the communication frequency command value is
between lower limit and upper limit frequencies
ILLEGAL FUNCTION exception
(Modbus exception code 01)
The indicated Modbus function is not supported: refer to section 12.2
for a list of supported functions
ILLEGAL DATA ADDRESS exception
(Modbus exception code 02)
The targeted drive register (or one in a group of targeted registers)
does not exist: check the drive’s supported register list
ILLEGAL DATA VALUE exception
(Modbus exception code 03)
The value written was rejected by the drive as invalid: check the value
and drive setting range
NEGATIVE ACKNOWLEDGE
exception (Modbus exception code 07)
• An attempt was made to write to a drive register while the drive
was running that does not accept writes while the drive is
running
• An attempt was made to write to a read-only register
• Confirm that the drive communication cable is fully seated into
the drive’s and ETH-100’s communication ports
• Confirm that the drive communication cable is not routed near
the drive’s input power or motor wiring or any other electrical
noise-producing cables or equipment
GATEWAY PATH UNAVAILABLE
exception (Modbus exception code 0A)
Unit Identifier (UI) was invalid: UI must be 1 ∼ 3
GATEWAY TARGET DEVICE FAILED
TO RESPOND exception (Modbus
exception code 0B)
The targeted drive is not online or failed to respond:
• Confirm that the targeted drive is powered-on
• Confirm that the drive communication cable is fully seated into
the drive’s and ETH-100’s communication ports
• Confirm that the drive communication cable is not routed near
the drive’s input power or motor wiring or any other electrical
noise-producing cables or equipment