Xantrex Technology ACCB Power Supply User Manual


 
Wiring for Off-Grid Applications using an AC Distribution Panel and an Internal Generator Disconnect
975-0046-01-01 1–25
To make the hot connections:
1. Connect the factory-installed hot (black) wire from the Inverter Input
Breaker in the ACCB to the AC2 GEN terminal in the inverter.
2. Connect the factory-installed hot wire (black) from the Inverter
Output Breaker in the ACCB to the INV OUT terminal in the inverter.
3. Connect a hot (black) wire from the AC OUT in the ACCB to the
HOT IN on the AC distribution panel.
4. Connect another hot (black) wire from the generator disconnect
breaker to the AC IN terminal in the ACCB.
5. Connect the hot (black) wire from the generator to the top of the
generator disconnect breaker.
Figure 1-21
Hot Connections for an Off-Grid Application with an AC Distribution Panel and an
Internal Generator Disconnect
Inverter Output
Breaker
Inverter Input Breaker
3
2
1
4
5