Wiring for On-Grid Applications Using Additional Circuit Breakers in the ACCB Only
975-0046-01-01 1–35
To make the ground connections:
1. Prepare the primary system ground and connect it to the ground bar in
the main AC distribution panel. See the Sine Wave Plus Inverter/
Charger Owner’s Manual for information regarding preparing the
primary system ground.
2. Route cable(s) (hot, neutral, and ground) from the main AC
distribution panel through one of the knockouts prepared in the
ACCB and connect the ground wire (green) to the ground bar in the
ACCB.
3. Connect the factory-installed ground wire (green) in the ACCB to the
AC ground bar in the inverter.
4. Connect the ground wire (green) from the generator to the ground bar
in the main AC distribution panel.
5. Route and connect a ground wire to the outlet that will be supporting
the AC load.
Figure 1-31
Ground Connections for an On-grid Application Using Additional Circuit Breakers
in the ACCB Only
1
3
2
4
5