Wiring for Off-Grid Applications Using Additional Circuit Breakers in the ACCB Only
975-0046-01-01 1–29
To make the hot connections:
1. Connect the factory-installed hot (black) wire from the Inverter Input
Breaker in the ACCB to the AC2 GEN terminal in the inverter
2. Connect the factory-installed hot wire (black) from the Inverter
Output Breaker in the ACCB to the INV OUT terminal in the inverter.
3. Connect another hot (black) wire from the generator disconnect
breaker to the AC IN terminal in the ACCB. Connect the other end of
that same hot (black) wire to the bottom of the generator disconnect
breaker.
4. Connect another hot (black) wire from the AC OUT terminal in the
ACCB to the bottom of the new circuit breaker.
5. Connect the hot (black) wire from the generator to the top of the
generator disconnect breaker.
6. Connect another hot (black) wire from the top of the additional circuit
breaker to the outlet that will support the AC load.
Figure 1-25
Hot Connections for an Off-grid Application with Additional Circuit Breakers
in the ACCB
Inverter Input
Breaker
Inverter Output
Breaker
2
3
1
4
5
6