Xantrex Technology XDC 20-300 Power Supply User Manual


 
Operation
3–12 TM-XDOP-01XN
To set the Over-Current Protection:
To set the Under-Current Protection:
Step # Do This You Will See
1 OVP SET 0V
2
Press repeatedly until the
desired setting appears.
OCP SET 0A
3OCP SET 0A
4 Use the Current knob, the numeric
keypad, or the arrow keys to enter a
value (0–103% of the unit’s rated
current).
OCP SET ####A
5 S/D if trip? N
6 Use the arrow keys to select Yes or No.
For this example, Yes is selected.
S/D if trip? Y
7 This setting is saved and the display
returns to its default operating mode.
PROT SET
ALARMS
PROT SET
ALARMS
ENTER
ENTER
ENTER
Step # Do This You Will See
1 OVP SET 0V
2
Press repeatedly until the desired setting
appears.
UCP SET 0A
3UCP SET 0A
4 Use the Current knob, the numeric keypad, or the
arrow keys to enter a value. The value must be
between 0–103% of the unit’s rated current.
UCP SET ####A
5 S/D if trip? N
6 Use the arrow keys to select Yes or No. For this
example, Yes is selected.
S/D if trip? Y
7 This setting is saved and
the display returns to its
default operating mode.
PROT SET
ALARMS
PROT SET
ALARMS
ENTER
ENTER
ENTER
TM-XDOP-01XN.book Page 12 Monday, July 17, 2006 11:19 AM