The connection to ground of the supplementary
equipment grounding conductor shall be in compli-
ance with the rules for terminating bonding jumpers
at Part K or Article 250 of the National Electrical
Code, ANSI/NFPA 70.
Termination of the supplementary equipment
grounding conductor is permitted to be made to
building steel, to a metal electrical raceway system, or
to any grounded item that is permanently and reli-
ably connected to the electrical service equipment
ground.
The supplemental grounding conductor shall be con-
nected to the equipment using a number 8 ring termi-
nal.
The terminal should be fastened to the grounding lug
provided on the rear panel of the equipment.
The ring terminal should be installed using the ap-
propriate crimping tool (AMP P/N 59250 T-EAD
Crimping Tool or equivalent).
Do not use this product near water, such as in a wet basement.
For DC-powered devices, the supply power for the product must be
installed near the equipment and be easily accessible.