American Power Conversion InfraStruXureTM System Power Supply User Manual


 
30 InfraStruXure System—Installation and Start-Up
Connect DC Power Wiring
Electrical
Hazar
d
Only qualified personnel trained by APC may connect the Battery Enclosure to
the Symmetra PX UPS or to another Battery Enclosure.
Warning
The supplied power and ground wires are for internal side-panel wiring only.
These wires are not for use in external conduits.
Electrical
Hazar
d
Before you begin connecting the DC power wiring, ensure that there are no
battery units installed in the Battery Enclosures. Do not install battery units until
instructed to do so.