American Power Conversion InfraStruXureTM System Power Supply User Manual


 
Appendix A : System Operation
72 InfraStruXure System—Installation and Start-Up
c. Select UPS Into Bypass on the Control menu, and
press the
E
NTER
key.
Control Menu
d. Confirm the selection on the next screen: select Yes,
UPS into Bypass, and press the
E
NTER
key.
Confirmation Screen
Note
The H2 LED above the Q2 circuit breaker illuminates, indicating that it is
safe to operate the Q2 circuit breaker.
7. Close (turn ON) the Q2 circuit breaker on the PDU.
Note
The H3 LED above the Q3 circuit breaker illuminates, indicating that it is safe to
operate the Q3 circuit breaker
8. Open (turn OFF) the Q3 circuit breaker on the PDU.
The UPS automatically comes out of Static Bypass
operation.
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load On
Confirm
Yes, UPS into Bypass
No, Abort